Plan Review Notes For Permit 18010481 |
Permit Number |
18010481 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-01-30 18:58:52 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE GENERATOR PAD PLANS HAVE SEVERAL REFERENCES TO | | THE FBC FIFTH EDITION (2014). THE FBC SIXTH EDITION | | (2017) WENT INTO EFFECT ON JANUARY 1, 2018. ALL NEW | | PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED | | TO COMPLY WITH AND REFERENCE THE FBC SIXTH EDITION | | (2017). | | | | 2) THE MODEL NUMBER FOR THE 16 KW GENERAC GENERATOR | | FROM THE MANUFACTURER'S SPECIFICATIONS THAT WERE | | SUBMITTED IS NOT ON THE PAD PLANS THAT WERE SUBMITTED. | | FBC 107.2.1 | | | | 3) THE GENERATOR PAD AND ANCHORING PLANS ARE REQUIRED | | TO HAVE THE FLORIDA ENGINEER'S SEAL AND ORIGINAL | | HANDWRITTEN SIGNATURE, COPIES OR OTHER FACSIMILES ARE | | NOT ACCEPTABLE. FAC 61G15 - 23.002 |
|