2018-01-30 18:58:52PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD PLANS HAVE SEVERAL REFERENCES TO
 THE FBC FIFTH EDITION (2014). THE FBC SIXTH EDITION
 (2017) WENT INTO EFFECT ON JANUARY 1, 2018. ALL NEW
 PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED
 TO COMPLY WITH AND REFERENCE THE FBC SIXTH EDITION
 (2017).
  
 2) THE MODEL NUMBER FOR THE 16 KW GENERAC GENERATOR
 FROM THE MANUFACTURER'S SPECIFICATIONS THAT WERE
 SUBMITTED IS NOT ON THE PAD PLANS THAT WERE SUBMITTED.
 FBC 107.2.1
  
 3) THE GENERATOR PAD AND ANCHORING PLANS ARE REQUIRED
 TO HAVE THE FLORIDA ENGINEER'S SEAL AND ORIGINAL
 HANDWRITTEN SIGNATURE, COPIES OR OTHER FACSIMILES ARE
 NOT ACCEPTABLE. FAC 61G15 - 23.002