Text |
2018-01-30 13:48:09 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE |
| CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE |
| CURRENT CODE ABOVE) |
| 2. BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, |
| 15- AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| SHALL BE AFCI PROTECTED. PROVIDE CORRECTION. NEC |
| 210.12; FBC RE E3902.16 |
| 3. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 |
| 4. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL |
| HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| 210.8(A)(9); FBC RE E3902.9 |
| 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| 210.8(D); FBC RE E3902.10 |
| 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 |
| . |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |