2018-03-28 08:02:48 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 18010368 |
| ADD: 2481 OKEECHOBEE BLVD. |
| CONT: TBD/ TO BE DETERMINED |
| TEL: 561-822-7650 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: WED. MARCH 28, 2018 |
| ACTION: DENIED. |
| |
| 1)PROVISO: DEFERRED SUBMITTAL / 2017 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, INTAKE AND EXHAUST |
| FANS & ROOF TOP VENTILATORS |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 2) PROVISO: PLEASE IDENTIFY ON THE PRODUCT APPROVAL |
| BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE |
| SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS |
| WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & |
| HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH IF |
| UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED, |
| ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING |
| SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE |
| CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN |
| THE TESTS. |
| |
| 3)PROVISO: ROOFING: FOR ALL ROOFING PRODUCTS PLEASE |
| IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED |
| PRESSURES FOR ROOF ZONE # 1. REVIEW THE PRODUCT |
| APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED |
| FOR ROOF ZONES 2 & 3. FASTENER DENSITIES SHALL BE |
| INCREASED FOR BOTH INSULATION & THE BASE SHEET AS |
| CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION |
| STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND |
| SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| CLADDING. |
| |
| 4)PROVISO: SHEET S-403 DETAIL # 1 SHOW A NEW MECHANICAL |
| STAND WITH A VERTICAL DISTANCE MEASURED 48 INCHES FROM |
| THE TOP OF THE BAR JOIST TO THE BOTTOM OF THE |
| CONDENSING UNIT. THE 2017 FBC-B TABLE 1510.10 STATES |
| CLEARANCE BELOW RAISED ROOF MOUNTED MECHANICAL UNITS. |
| FOR A UNIT 60 INCHES IN WIDTH OR WIDER THERE IS TO BE |
| 48 INCHES OF CLEARANCE. THE WAY THE DISTANCE IS |
| MEASURED YOU DO NOT HAVE 48 INCHES CLEARANCE. |
| DEFINITION: THE DISTANCE BY WHICH ONE OBJECT CLEARS |
| ANOTHER OR THE CLEAR SPACE BETWEEN THEM. |
| |
| 5) PROVISO: THE S-403 DETAIL 1 NOR THE H DRAWINGS SHOW |
| HOW THE ROOF TOP CONDENSERS ARE GOING TO BE ANCHORED TO |
| RESIST SLIDING OR THE MOMENT OF OVERTURNING. 2017 FBC-B |
| 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL MEMBERS AND |
| THEIR CONNECTIONS SHALL BE DETERMINED BY METHODS OF |
| STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM, |
| GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH |
| SHORT- AND LONG-TERM MATERIAL PROPERTIES. EVERY |
| STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING |
| EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS |
| CHAPTER. SEE SECTION 1609 FOR WIND LOADS. |
| |
| 6-8) COMPLIED. |
| |
| 9) THE RESPONSE INDICATED THE TENANT WOULD LIKE A |
| RESIDENT INSPECTOR ON SITE FOR THE STEEL AND CONCRETE |
| WORK. FORMS WERE E-MAILED TO: |
| [email protected] CAME BACK UNDELIVERABLE |
| [email protected] 3/27/2018 04:46 PM |
| |
| FORMS NEED TO BE SIGNED AND RETURNED BEFORE PERMIT |
| ISSUANCE. |
| |
| ONLY (2) SETS OF PLANS WERE SUBMITTED, (3) SETS |
| REQUIRED FOR RESIDENT INSPECTOR!!!!!!! |
| |
| 10) COMPLIED. |
| |