Plan Review Notes
Plan Review Notes For Permit 18010368
Permit Number 18010368
Review Stop B
Sequence Number 2
Notes
Date Text
2018-03-28 08:02:482017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18010368
 ADD: 2481 OKEECHOBEE BLVD.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-822-7650
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. MARCH 28, 2018
 ACTION: DENIED.
  
 1)PROVISO: DEFERRED SUBMITTAL / 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, INTAKE AND EXHAUST
 FANS & ROOF TOP VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 2) PROVISO: PLEASE IDENTIFY ON THE PRODUCT APPROVAL
 BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE
 SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS
 WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH &
 HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH IF
 UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 3)PROVISO: ROOFING: FOR ALL ROOFING PRODUCTS PLEASE
 IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED
 PRESSURES FOR ROOF ZONE # 1. REVIEW THE PRODUCT
 APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED
 FOR ROOF ZONES 2 & 3. FASTENER DENSITIES SHALL BE
 INCREASED FOR BOTH INSULATION & THE BASE SHEET AS
 CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION
 STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 4)PROVISO: SHEET S-403 DETAIL # 1 SHOW A NEW MECHANICAL
 STAND WITH A VERTICAL DISTANCE MEASURED 48 INCHES FROM
 THE TOP OF THE BAR JOIST TO THE BOTTOM OF THE
 CONDENSING UNIT. THE 2017 FBC-B TABLE 1510.10 STATES
 CLEARANCE BELOW RAISED ROOF MOUNTED MECHANICAL UNITS.
 FOR A UNIT 60 INCHES IN WIDTH OR WIDER THERE IS TO BE
 48 INCHES OF CLEARANCE. THE WAY THE DISTANCE IS
 MEASURED YOU DO NOT HAVE 48 INCHES CLEARANCE.
 DEFINITION: THE DISTANCE BY WHICH ONE OBJECT CLEARS
 ANOTHER OR THE CLEAR SPACE BETWEEN THEM.
  
 5) PROVISO: THE S-403 DETAIL 1 NOR THE H DRAWINGS SHOW
 HOW THE ROOF TOP CONDENSERS ARE GOING TO BE ANCHORED TO
 RESIST SLIDING OR THE MOMENT OF OVERTURNING. 2017 FBC-B
 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL MEMBERS AND
 THEIR CONNECTIONS SHALL BE DETERMINED BY METHODS OF
 STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM,
 GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH
 SHORT- AND LONG-TERM MATERIAL PROPERTIES. EVERY
 STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING
 EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS
 CHAPTER. SEE SECTION 1609 FOR WIND LOADS.
  
 6-8) COMPLIED.
  
 9) THE RESPONSE INDICATED THE TENANT WOULD LIKE A
 RESIDENT INSPECTOR ON SITE FOR THE STEEL AND CONCRETE
 WORK. FORMS WERE E-MAILED TO:
 [email protected] CAME BACK UNDELIVERABLE
 [email protected] 3/27/2018 04:46 PM
  
 FORMS NEED TO BE SIGNED AND RETURNED BEFORE PERMIT
 ISSUANCE.
  
 ONLY (2) SETS OF PLANS WERE SUBMITTED, (3) SETS
 REQUIRED FOR RESIDENT INSPECTOR!!!!!!!
  
 10) COMPLIED.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  