Plan Review Notes For Permit 18010368 |
Permit Number |
18010368 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-02-22 11:42:16 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | PLUMBING COMMENTS: | | | | 1. SHT. D-101 IF NO WORK IS BEING DONE IN BATHROOMS | | PLEASE SHOW LOCATION OF FIXTURE AND NOTE ON THE PLAN | | EXISTING TO REMAIN. PER WPB AMEND TO FBC 107.2.1 | | | | 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE RPZ | | BACKFLOW TO VERIFY THAT IT MEETS THE LEAD FREE | | REQUIREMENTS. PER WPB AMEND TO FBC 107.2.1 | | | | 3. SHT. A-513 DETAIL D3 HAS NOTE REF EVAC SYSTEM SEE | | REFRIGERATION DRAWING NON ARE PROVIDED IN PLAN SET, A | | VACUUM SYSTEM PIPING DIAGRAM WILL BE REQUIRED IN THE | | PLAN SET FOR REVIEW. PER WPB AMEND TO FBC 107.2.1 | | | | 4. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR THE | | EVAC SYSTEM. PER WPB AMEND TO FBC 107.2.1 | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|