2018-02-12 10:45:521ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18010368
 2/12/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET H-101: PROVIDE THE TYPE AND SIZE OF THE NEW
 DUCTWORK- NOTE H2.
  
 2) H-101: PROVIDE AND AIR DEVICE SCHEDULE.
  
 3) H-101: NOTES H1 AND H5 ARE IN CONFLICT. NOTE H1
 SPECIFIES PAINTED DUCTWORK HOWEVER NOTE H5 INDICATES
 THE DUCTS TO BE INSULATED. PLEASE NOTE FIBERGLASS
 INSULATION AND/OR FIREGLASS DUCTWORK SHALL NOT BE
 PAINTED PER THE UL LISTINGS AND FLAMESPEAD
 SMOKE-DEVELOPED INDEX OF THE MATERAL.
  
 4) PROVIDE SUPPORT AND HANGING DETAILS FOR THE NEW
 DUCTWORK PER SMACNA HVAC DUCT CONSTRUCTION STANDARDS-
 2005.
  
 5) COMCHECK REPORT: PROVIDE COMPLIANCE DATA FOR THE
 HVAC ALTERATIONS.
  
 6) ADVISORY: THE ARCHITECTURAL AND ELECTRICAL PLANS ARE
 SHOWING ALERATIONS TO THE REFRIGERATIONS SYTEMS. PLEASE
 NOTE THAT THE CITY OF WEST PALM BEACH REQUIRES A
 SEPARATE PERMIT FOR REFRIGERATION SYSTEMS FOR FOOD
 CASES, WALK-IN BOXES ETC. COMPLETE PLANS AND
 SPECIFICATIONS MUST BE SUBMITTED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  