2018-02-12 10:45:52 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18010368 |
| 2/12/18 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET H-101: PROVIDE THE TYPE AND SIZE OF THE NEW |
| DUCTWORK- NOTE H2. |
| |
| 2) H-101: PROVIDE AND AIR DEVICE SCHEDULE. |
| |
| 3) H-101: NOTES H1 AND H5 ARE IN CONFLICT. NOTE H1 |
| SPECIFIES PAINTED DUCTWORK HOWEVER NOTE H5 INDICATES |
| THE DUCTS TO BE INSULATED. PLEASE NOTE FIBERGLASS |
| INSULATION AND/OR FIREGLASS DUCTWORK SHALL NOT BE |
| PAINTED PER THE UL LISTINGS AND FLAMESPEAD |
| SMOKE-DEVELOPED INDEX OF THE MATERAL. |
| |
| 4) PROVIDE SUPPORT AND HANGING DETAILS FOR THE NEW |
| DUCTWORK PER SMACNA HVAC DUCT CONSTRUCTION STANDARDS- |
| 2005. |
| |
| 5) COMCHECK REPORT: PROVIDE COMPLIANCE DATA FOR THE |
| HVAC ALTERATIONS. |
| |
| 6) ADVISORY: THE ARCHITECTURAL AND ELECTRICAL PLANS ARE |
| SHOWING ALERATIONS TO THE REFRIGERATIONS SYTEMS. PLEASE |
| NOTE THAT THE CITY OF WEST PALM BEACH REQUIRES A |
| SEPARATE PERMIT FOR REFRIGERATION SYSTEMS FOR FOOD |
| CASES, WALK-IN BOXES ETC. COMPLETE PLANS AND |
| SPECIFICATIONS MUST BE SUBMITTED. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |