2018-02-14 13:44:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 2. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND DATA
 SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. FBC 105.1, 107.2.1
 3. ELECTRICAL LOAD SUMMARY STATES THAT NEC 220.87 IS
 USED TO DETERMINE EXISTING LOAD. PROVIDE THE 12 MONTH
 HISTORY TO CONFIRM STATED DEMAND LOAD ON PLAN. FBC
 107.2.1, NEC 220.87
 4. ELECTRICAL LOAD SUMMARY SHOWS THAT A TOTAL OF 65.2
 KVA IS BEING ADDED TO PANEL DP1. THE PANEL SCHEDULE
 SHOWS A LOAD OF 101.52 KVA FOR CDRU AND 47.1 KVA FOR
 REMOTE DEFROST PANEL, WHICH WOULD BE A TOTAL OF 148.62
 KVA, PLUS OTHER ADDITIONAL LOADS FROM THE SUMMARY
 TOTALING 12.3 KVA, FOR A GRAND TOTAL OF 160.92 KVA.
 THIS WOULD OVERLOAD THE EXISTING PANEL AND TRANSFORMER
 FEEDING PANEL DP1. PROVIDE CLARIFICATION AND/OR
 CORRECTION. NEC 215.2, 220, 408.30: FBC 107.2.1
 5. PROVIDE LOAD CALCULATION FOR 400 AMP, 3 PHASE,
 277/480 VOLT SYSTEM. ARE THERE ANY LOADS BEING FED FROM
 THIS AHEAD OF THE TRANSFORMER FOR PANEL DP1? IF NOT,
 DISREGARD THIS REQUEST. NEC 215.2, 220, 408.30: FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  