2018-02-01 16:19:18 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 18010368 |
| ADD: 2481 OKEECHOBEE BLVD. |
| CONT: TBD/ TO BE DETERMINED |
| TEL: 561-822-7650 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. FEB. 01/ 2018 |
| ACTION: DENIED |
| |
| 1) SHEET A-101: AT DOOR 102B THERE IS A SECTION THROUGH |
| THE DOOR NO NOMENCLATURE, NOT COMPLETE XX/XXX. |
| ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.3. UNKNOWN |
| IF THE EXISTING DOOR IS A 3 FOOT DOOR THAT IS BEING |
| INCREASED TO A 4 FOOT WIDE DOOR THE STRUCTURAL PLAN |
| S-102 IS ALSO SILENT ON THIS DOOR OPENING? |
| |
| 2) SHEET A-601: |
| 2A) PLEASE REVIEW THE DOOR SCHEDULE 101A IS LABELED 7 |
| FT. 6 IN. LISTED AS ELEVATION DD BUT THE DETAIL |
| INDICATES THE DOOR TO BE 8 FT. THEN VERIFY. DISCREPANCY |
| IN HEIGHT. THE STRUCTURAL SHEET S-201 SOUTH ELEVATION |
| FRAMING SHOWS A HORIZONTAL 6X6 HSS STEEL BEAM BUT NO |
| ELEVATION IS GIVEN, SHEET S-401 |
| DETAIL # 4 SHOWS THE SAME 6X6 HSS STEEL BEAM AND NO |
| ELEVATION IS PROVIDED. AGAIN NO ELEVATION HAS BEEN |
| PROVIDED FOR THIS BEAM. |
| |
| 2B) SHEET A-101 SHOWS DOORS 101B & 101C BOTH AS A |
| SINGLE SWING DOOR, SHEET A-601 DEPICTS THESE DOORS AS |
| TYPE EE. SHEET A-602 INDICATES BOTH SETS OF DOORS ARE |
| AUTO SLIDING DOORS. PLEASE NOTE AS DEPICTED THERE IS NO |
| HORIZONTAL MULLION BETWEEN THE UPPER TRANSOM AND AUTO |
| DOOR MECHANISM HOUSING. |
| NOTE ALSO INDICATES THAT THE AUTOMATIC DOORS ARE |
| PROVIDED BY A ALDI VENDOR. ARE THE DOORS NEW DOORS, OR |
| RE-USED DOORS? IS THE VENDOR TO BE COVERED UNDER THIS |
| PERMIT? DOES THE ALDI VENDOR HAVE FLORIDA CONTRACTING |
| LICENSURE TO DO THIS TYPE OF INSTALLATION? |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 3) SHEET G-002 LIST 9 PRODUCT APPROVALS, THESE PRODUCT |
| APPROVALS WERE NOT SUBMITTED THIS REVIEW CYCLE. THE |
| DESIGNER OF RECORD CAN DEFER THE SUBMISSION OF THESE |
| APPROVALS UNTIL AFTER PERMIT ISSUANCE. PLEASE NOTE IN |
| THE NARRATIVE RESPONSE IF THE PRODUCT APPROVALS ARE TO |
| BE CONSIDERED A DEFERRED SUBMITTAL. |
| |
| 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 4) REQUIRED PRODUCT APPROVALS. 2017 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, INTAKE AND EXHAUST |
| FANS & ROOF TOP VENTILATORS |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 5) PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B |
| 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| |
| 6) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| CALCULATION PREPARED, SIGNED AND |
| SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| CLADDING. |
| |
| 7A) SHEET S-403 DETAIL # 1 SHOW A NEW MECHANICAL STAND |
| WITH A VERTICAL DISTANCE MEASURED 48 INCHES FROM THE |
| TOP OF THE BAR JOIST TO THE BOTTOM OF THE CONDENSING |
| UNIT. THE 2017 FBC-B TABLE 1510.10 STATES CLEARANCE |
| BELOW RAISED ROOF MOUNTED MECHANICAL UNITS. FOR A UNIT |
| 60 INCHES IN WIDTH OR WIDER THERE IS TO BE 48 INCHES OF |
| CLEARANCE. THE WAY THE DISTANCE IS MEASURED YOU DO NOT |
| HAVE 48 INCHES CLEARANCE. |
| DEFINITION: THE DISTANCE BY WHICH ONE OBJECT CLEARS |
| ANOTHER OR THE CLEAR SPACE BETWEEN THEM. |
| |
| 7B) THE S-403 DETAIL 1 NOR THE H DRAWINGS SHOW HOW THE |
| ROOF TOP CONDENSERS ARE GOING TO BE ANCHORED TO RESIST |
| SLIDING OR THE MOMENT OF OVERTURNING. 2017 FBC-B 1604.4 |
| ANALYSIS. LOAD EFFECTS ON STRUCTURAL MEMBERS AND THEIR |
| CONNECTIONS SHALL BE DETERMINED BY METHODS OF |
| STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM, |
| GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH |
| SHORT- AND LONG-TERM MATERIAL PROPERTIES. EVERY |
| STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING |
| EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS |
| CHAPTER. SEE SECTION 1609 FOR WIND LOADS. |
| |
| 8) SHEET S-002. PRESSURES FOR ROOF ZONES ARE GOOD, THE |
| PRESSURES FOR WALL ZONES 4 & 5 APPEAR LOW. 2017 FBC-B |
| 1603.1.4 WIND DESIGN DATA. ASSUMED MEAN ROOF HEIGHT OF |
| 25 FEET. |
| WALL ZONE 4 AT 10 SQ FT. 3.6 PSF LOW |
| 20 SQ . FT.3.2 PSF LOW |
| 50 SQ. FT. 2.8 PSF LOW |
| 100 SQ. FT. 1.2 PSF LOW |
| |
| WALL ZONE 5 AT 10 SQ. FT. 3.4 PSF LOW |
| 20 SQ. FT. 3.2 PSF LOW. |
| 50 SQ. FT. 3.0 PSF LOW. |
| 100 SQ. FT. 1.1 PSF LOW. |
| |
| 9) PLEASE NOTE THIS PROJECT MAY BE CONSIDERED FOR A |
| RESIDENT INSPECTOR PROGRAM BECAUSE OF THE STEEL OR THE |
| CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| STANDARDS AT TIME OF INSPECTION. |
| 2017 FBC-B 2204.1 WELDING |
| 2017 FBC-B 2204.2 BOLTING. |
| |
| 10) THE SHEET A-131 SHOWS 6 CHECKOUT LANES BUT THERE |
| ARE NO DETAILS PROVIDING COMPLIANCE WITH THE 2017 |
| ACCESSIBILITY CODE SECTION 904.3 CHECK-OUT AISLES. |
| 904.3.2 COUNTER. THE COUNTER SURFACE HEIGHT SHALL BE 38 |
| INCHES (965 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| GROUND. THE TOP OF THE COUNTER EDGE PROTECTION SHALL BE |
| 2 INCHES (51 MM) MAXIMUM ABOVE THE TOP OF THE COUNTER |
| SURFACE ON THE AISLE SIDE OF THE CHECK-OUT COUNTER. |
| |
| 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |