Plan Review Notes
Plan Review Notes For Permit 18010351
Permit Number 18010351
Review Stop G
Sequence Number 1
Notes
Date Text
2018-01-23 05:54:0101/23/2018 GAS 1ST REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) CITY PERMIT AND INSPECTION RECORDS SHOW THE TOTAL
 LOAD ON THE SYSTEM AS 982,000 BTU. IT SEEMS YOU HAVE
 NOT INCLUDED THE POOL HEATER AND ANOTHER APPLIANCE
 INSIDE. LIST THE BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017
 FBC-FUEL GAS SECS.401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2413.
  
 2) CITY PERMIT AND INSPECTION RECORDS SHOW THIS SYSTEM
 AS A 12" W.C AND NOT 2 PSI. IS IT YOU IN INTENTIONS TO
 UPGRADE THIS SYSTEM TO A 2PSI FROM 12" W.C SYSTEM? IF
 SO PLEASE ADVISE ON PLAN. FBC 107.2.1
  
 3) CITY PERMIT AND INPSECTION RECORDS DO NOT SHOW ANY
 UNDERGROUND P.E PIPING ON THIS PROPERTY. IF THIS
 UNDERGROUND P.E EXIST IT WILL NEED TO BE EXPOSED AT THE
 JOINTS. TESTED TO COMPLY WITH FBC 406 AND HAVE THE DATE
 CODE ON THE PIPING VISABLE. FBC 107.2.1
  
 4) SIZE AND LENGHT OF PIPING COMING OFF OF METER
 MISSING ON ISOMETRIC.SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2014
 FBC-RES SEC. G2413.
  
 5) GENERATOR SPEC SHOW IT AS A 20KW BUT ON YOU GAS
 ISOMETRIC IT IS SHOWN AS 22KW. FBC 107.2
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  