Plan Review Notes
Plan Review Notes For Permit 18010302
Permit Number 18010302
Review Stop B
Sequence Number 2
Notes
Date Text
2018-01-18 16:36:40RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017)
  
 ORIGINAL COMMENT:
 1- PROVIDE PRODUCT APPROVAL THAT MEETS THE DESIGN
 PRESSURES FOR EXPOSURE "C". DRAWINGS SUBMITTED WITH
 FLORIDA PRODUCT APPROVAL FL17347-R2 DON'T MEET THOSE
 DESIGN PRESSURES.
 FAC 61G20-3.001
  
 RESPONSE:
 SAME DRAWING FL17347.15 WAS RE-SUBMITTED. IT DOESN'T
 MEET THE DESIGN PRESSURES SHOWN ON WIND-LOADS
 SUBMITTED. THE REPLACEMENT DOOR IS A SINGLE DOOR WITH
 SIDELITE ASSEMBLY. THEREFORE, THE DESIGN PRESSURES FOR
 A SINGLE DOOR WITH SIDELITE ASSEMBLY (OX/XO) SHOWN ON
 PRODUCT APPROVAL SUBMITTED DON'T MEET THE DESIGN
 PRESSURES. CONTRACTOR MARKED THE SINGLE DOOR ONLY. THIS
 IS INCORRECT. PROVIDE PRODUCT APPROVAL THAT MEETS THE
 DESIGN PRESSURES SHOWN ON THE WIND LOAD TABLE SUBMITTED
 FOR THE DOOR WITH SIDELITE ASSEMBLY.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]