Plan Review Notes
Plan Review Notes For Permit 18010302
Permit Number 18010302
Review Stop B
Sequence Number 1
Notes
Date Text
2018-01-11 18:14:57RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC 6TH EDITION (2017)
  
 1- WIND LOAD CALCULATIONS SUBMITTED ARE MARKED WITH THE
 DESIGN PRESSURES FOR AN INTERIOR ZONE IN EXPOSURE "B".
 ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL, THIS
 BUILDING IS LOCATED IN EXPOSURE "C" NOT EXPOSURE.
 REVISE AS REQUIRED. OR PROVIDE COMPLETE ENGINEERING
 ANALYSIS WITH CALCULATIONS FOR ALL WIND DIRECTIONS.
  
 2- PROVIDE PRODUCT APPROVAL THAT MEETS THE DESIGN
 PRESSURES FOR EXPOSURE "C". DRAWINGS SUBMITTED WITH
 FLORIDA PRODUCT APPROVAL FL17347-R2 DON'T MEET THOSE
 DESIGN PRESSURES.
 FAC 61G20-3.001
  