2018-03-15 10:07:03 | PLAN |
| REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE |
| ENERGY FORM R405-2017. FBC ENERGY CONSERVATION |
| R103.1.1.2 |
| |
| 2) THE ICP POLYSET RTA-1, ROOF TILE ADHESIVE THAT WAS |
| SUBMITTED (NOA NO. 16-0315.03) IS NOT ONE OF THE |
| APPROVED ADHESIVES THAT IS LISTED IN THE ENTEGRA ROOF |
| TILE NOA NO. 1--0421.08. THE RTA-1 PRODUCT APPROVAL |
| STATES THAT IT CAN BE USED WITH ANY ROOF TILE ASSEMBLY |
| HAVING A CURRENT NOA THAT LISTS ATTACHMENT RESISTANCE |
| VALUES WITH ITS USE. THIS TILE NOA DOES NOT LIST IT. |
| SUBMIT TWO SETS OF PRODUCT APPROVALS FOR A ROOF TILE |
| ADHESIVE THAT IS APPROVED FOR USE WITH THE TILE. FBC |
| 107.3.4 & FAC 61G20-3.001 |
| |
| 3) THE WINDOW SCHEDULE SPECIFIES DOUBLE HUNG WINDOWS |
| AND THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR |
| SINGLE HUNG WINDOWS. PLEASE COORDINATE THE PRODUCT |
| APPROVALS WITH THE PLANS. FBC 107.2.1 (REPEAT COMMENT) |
| |
| 4) THE PLANS REQUIRE DESIGN PRESSURES OF +47.8 AND |
| -59.31 FOR THE SECTIONAL GARAGE DOORS. THE MAXIMUM |
| DESIGN LOADS LISTED IN PRODUCT APPROVALS FOR THE |
| SECTIONAL GARAGE DOORS IS +46 AND -52 PSF WHICH DO NOT |
| MEET THE REQUIRED DESIGN PRESSURES. FBC-R301.2.1.1 |
| NOTE: TABLE R301.2(4) IN THE FBC RESIDENTIAL HAS LOWER |
| DESIGN PRESSURE FOR GARAGE DOORS. (REPEAT COMMENT) |
| |
| 5) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |
| |