Plan Review Notes
Plan Review Notes For Permit 18010301
Permit Number 18010301
Review Stop B
Sequence Number 2
Notes
Date Text
2018-03-15 10:07:03PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY FORM R405-2017. FBC ENERGY CONSERVATION
 R103.1.1.2
  
 2) THE ICP POLYSET RTA-1, ROOF TILE ADHESIVE THAT WAS
 SUBMITTED (NOA NO. 16-0315.03) IS NOT ONE OF THE
 APPROVED ADHESIVES THAT IS LISTED IN THE ENTEGRA ROOF
 TILE NOA NO. 1--0421.08. THE RTA-1 PRODUCT APPROVAL
 STATES THAT IT CAN BE USED WITH ANY ROOF TILE ASSEMBLY
 HAVING A CURRENT NOA THAT LISTS ATTACHMENT RESISTANCE
 VALUES WITH ITS USE. THIS TILE NOA DOES NOT LIST IT.
 SUBMIT TWO SETS OF PRODUCT APPROVALS FOR A ROOF TILE
 ADHESIVE THAT IS APPROVED FOR USE WITH THE TILE. FBC
 107.3.4 & FAC 61G20-3.001
  
 3) THE WINDOW SCHEDULE SPECIFIES DOUBLE HUNG WINDOWS
 AND THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR
 SINGLE HUNG WINDOWS. PLEASE COORDINATE THE PRODUCT
 APPROVALS WITH THE PLANS. FBC 107.2.1 (REPEAT COMMENT)
  
 4) THE PLANS REQUIRE DESIGN PRESSURES OF +47.8 AND
 -59.31 FOR THE SECTIONAL GARAGE DOORS. THE MAXIMUM
 DESIGN LOADS LISTED IN PRODUCT APPROVALS FOR THE
 SECTIONAL GARAGE DOORS IS +46 AND -52 PSF WHICH DO NOT
 MEET THE REQUIRED DESIGN PRESSURES. FBC-R301.2.1.1
 NOTE: TABLE R301.2(4) IN THE FBC RESIDENTIAL HAS LOWER
 DESIGN PRESSURE FOR GARAGE DOORS. (REPEAT COMMENT)
  
 5) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  