Plan Review Notes
Plan Review Notes For Permit 18010301
Permit Number 18010301
Review Stop B
Sequence Number 1
Notes
Date Text
2018-02-08 11:50:15PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS HAVE SEVERAL REFERENCES TO THE FBC FIFTH
 EDITION (2014). THE FBC SIXTH EDITION (2017) WENT INTO
 EFFECT ON JANUARY 1, 2018. ALL NEW PERMITS APPLIED FOR
 ON OR AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE FBC SIXTH EDITION (2017). CHECK SHEETS:
 T-1, A-007, A-008, S-0, S-4 AND S-6
  
 2) ON SHEET T-1 THE ALLOWABLE STRESS DESIGN (V BASIC)
 WIND SPEED IS MISTAKENLY SPECIFIED AS 32 MPH AND IT
 SHOULD BE 132 MPH. FBC-R301.2.1
  
 3) SUBMIT TWO SETS OF A SURVEY OF THE PROPERTY. FBC
 107.2.1
  
 4) SUBMIT TWO SETS OF A SITE DRAINAGE PLAN WITH THE
 ELEVATIONS USING NAVD 88, WHICH IS THE VERTICAL DATUM
 USED ON THE CURRENT FLOOD MAPS. FBC 107.2.5 AND
 FBC-R401.3
  
 5) SEPARATE PERMIT APPLICATIONS ARE REQUIRED FOR THE
 DRIVEWAY, WALKS AND POOL.
  
 6) UPDATE THE EDITIONS OF THE STANDARDS THAT ARE LISTED
 ON SHEET S-4 TO THE ONES REFERENCED IN THE 2017 FBC-R.
 ACI 318-14, 332-14, 530-13, 530.1-13, TMS 402-16,
 403-2013, 602-2016 AND ASCE 5-13, 6-13.
  
 7) THIS PROJECT HAS A ROOF SLOPE OF 3:12. WALL SECTION
 2 ON SHEET A-008 HAS A NOTE FOR FOR 30 YEAR ASPHALT
 SHINGLES ON 30# FELT. FBC-R 905.2.2 REQUIRES TWO LAYERS
 OF UNDERLAYMENT ON ROOF SLOPES LESS THAN 4:12. REVISE
 NOTE.
  
 8) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY FORM R405-2017. FBC ENERGY CONSERVATION
 R103.1.1.2
  
 9) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 AH-160 ROOF TILE ADHESIVE (NOA NO. 14-0805.01) EXPIRED
 ON 5/10/2017. SUBMIT A CURRENT PRODUCT APPROVAL. FBC
 107.3.4 PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 PER
 FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE
 TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS
 INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN
 PRESSURES FOR EACH OF THE DIFFERENT ROOFING MATERIALS,
 WINDOW/GLASS TYPES, STRUCTURAL MULLIONS AND EXTERIOR
 DOOR TYPES.
  
 10) THE PRODUCT APPROVALS THAT WERE SUBMITTED DO NOT
 REFERENCE THE CURRENT 2017 FLORIDA BUILDING CODE.
 SUBMIT NEW PRODUCT APPROVALS THAT HAVE BEEN UPDATED TO
 THE 2017 FBC.
  
 11) THE NOA NO. ON THE PRODUCT APPROVAL LETTER FROM THE
 DESIGNER OF RECORD HAS THE WRONG NOA NO. FOR THE FRENCH
 DOORS. IT SHOULD BE NOA NO. 14-0908.07 NOT NOA NO.
 14-0809.07.
  
 12) A PRODUCT APPROVAL WAS SUBMITTED FOR SLIDING GLASS
 DOORS, HOWEVER, THERE ARE NOT ANY SLIDING GLASS DOORS
 SHOWN ON THE PLANS OR LISTED IN THE DOOR SCHEDULE.
 PLEASE CLARIFY. IF THERE ARE NO SLIDING GLASS DOORS,
 THEN REMOVE THE PRODUCT APPROVALS FROM THE PERMIT
 DOCUMENTS.
  
 13) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR STRUCTURAL
 MULLIONS. FBC 107.3.4
  
 14) THE WINDOW SCHEDULE SPECIFIES DOUBLE HUNG WINDOWS
 AND THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR
 SINGLE HUNG WINDOWS. PLEASE COORDINATE THE PRODUCT
 APPROVALS WITH THE PLANS. FBC 107.2.1
  
 15) THE PLANS REQUIRE DESIGN PRESSURES OF +47.8 AND
 -59.31 FOR THE SECTIONAL GARAGE DOORS. THE MAXIMUM
 DESIGN LOADS LISTED IN PRODUCT APPROVALS FOR THE
 SECTIONAL GARAGE DOORS IS +46 AND -52 PSF WHICH DO NOT
 MEET THE REQUIRED DESIGN PRESSURES. FBC-R301.2.1.1
 NOTE: TABLE R301.2(4) IN THE FBC RESIDENTIAL HAS LOWER
 DESIGN PRESSURE FOR GARAGE DOORS.
  
 16) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  