Date |
Text |
2018-01-29 08:25:29 | PROVISO - THE TEMPORARY TENTS REQUIRE BUILDING REVIEW |
| PER FBC BUILDING 3103 |
| |
| SECTION 3103 |
| TEMPORARY STRUCTURES |
| 3103.1 GENERAL. |
| THE PROVISIONS OF SECTIONS 3103.1 THROUGH 3103.4 SHALL |
| APPLY TO STRUCTURES ERECTED FOR A PERIOD OF LESS THAN |
| 180 DAYS. TENTS AND OTHER MEMBRANE STRUCTURES ERECTED |
| FOR A PERIOD OF LESS THAN 180 DAYS SHALL COMPLY WITH |
| THE FLORIDA FIRE PREVENTION CODE. THOSE ERECTED FOR A |
| LONGER PERIOD OF TIME SHALL COMPLY WITH APPLICABLE |
| SECTIONS OF THIS CODE. |
| 3103.1.1 CONFORMANCE. |
| TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE |
| STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, |
| ACCESSIBILITY, LIGHT, VENTILATION AND SANITARY |
| REQUIREMENTS OF THIS CODE AS NECESSARY TO ENSURE PUBLIC |
| HEALTH, SAFETY AND GENERAL WELFARE. |
| 3103.1.2 PERMIT REQUIRED. |
| TEMPORARY STRUCTURES THAT COVER AN AREA GREATER THAN |
| 120 SQUARE FEET (11.16 M2), INCLUDING CONNECTING AREAS |
| OR SPACES WITH A COMMON MEANS OF EGRESS OR ENTRANCE |
| THAT ARE USED OR INTENDED TO BE USED FOR THE GATHERING |
| TOGETHER OF 10 OR MORE PERSONS, SHALL NOT BE ERECTED, |
| OPERATED OR MAINTAINED FOR ANY PURPOSE WITHOUT |
| OBTAINING A PERMIT FROM THE BUILDING OFFICIAL. |
| 3103.2 CONSTRUCTION DOCUMENTS. |
| A PERMIT APPLICATION AND CONSTRUCTION DOCUMENTS SHALL |
| BE SUBMITTED FOR EACH INSTALLATION OF A TEMPORARY |
| STRUCTURE. THE CONSTRUCTION DOCUMENTS SHALL INCLUDE A |
| SITE PLAN INDICATING THE LOCATION OF THE TEMPORARY |
| STRUCTURE AND INFORMATION DELINEATING THE MEANS OF |
| EGRESS AND THE OCCUPANT LOAD. |
| 3103.3 LOCATION. |
| TEMPORARY STRUCTURES SHALL BE LOCATED IN ACCORDANCE |
| WITH THE REQUIREMENTS OF TABLE 602 BASED ON THE |
| FIRE-RESISTANCE RATING OF THE EXTERIOR WALLS FOR THE |
| PROPOSED TYPE OF CONSTRUCTION. |
| 3103.4 MEANS OF EGRESS. |
| TEMPORARY STRUCTURES SHALL CONFORM TO THE MEANS OF |
| EGRESS REQUIREMENTS OF CHAPTER 10 AND SHALL HAVE AN |
| EXIT ACCESS TRAVEL DISTANCE OF 100 FEET (30 480 MM) OR |
| LESS. |