Plan Review Notes For Permit 18010254 |
Permit Number |
18010254 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2018-04-25 09:55:04 | PLAN | | REVIEW COMMENTS | | | | 4TH REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE REQUIRED WIND DESIGN DATA IS MISSING FROM THE | | SIGN INSTALLATION DRAWINGS THAT WERE SUBMITTED. FBC | | 1603.1.4 | | | | 2) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | 3) THESE PLANS HAVE BEEN REVIEWED AND FOUND TO BE | | DEFICIENT 4 TIMES NOW, THEREFORE, THE PERSON | | RESPONSIBLE FOR THE DESIGN OF THESE DOCUMENTS IS | | REQUIRED TO MEET WITH ME PRIOR TO RESUBMITTING THE | | PLANS FOR THE 5TH TIME. |
|