Plan Review Notes
Plan Review Notes For Permit 18010194
Permit Number 18010194
Review Stop G
Sequence Number 1
Notes
Date Text
2018-01-09 15:43:4501/09/2018 GAS 1ST REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 ALSO WE ARE CURRENTLY USING THE 2017 6TH ED OF THE
 FLORIDA FUEL AND GAS.
  
 1) YOU DID NOT INCLUDE ANY MANUFACTURE SPECS OR
 INSTALLATION MANUAL FOR THE GENERATOR. CURRENTLY WE DO
 NOT SHOW ANY PERMIT OR APPLICATION FOR A PERMIT TO
 INSTALL A GENERATOR. SUBMIT MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2014 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2014 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1 OR YOU WILL NEED TO WAIT FOR THE MAIN
 GENERATOR PERMIT BEFORE YOUR SUB CAN BE ISSUED.
  
 2) CITY RECORDS SHOW YOUR ISOMETRIC AND BTU LOAD OF
 EXISTING NOT TO BE ACCURATE. BASED OFF CITY RECORDS THE
 ADDING OF ANY MORE BTU ON THE EXISTING 1" METALLIC PIPE
 OUTLET OF THE EXISTING 2LB METER WILL BE UNDERSIZED
 .THE EXISTING BTU LOAD OF THE EXISTING GAS SYSTEM MUST
 BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO
 ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF
 UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. . FGC SECS. 401.4, 401.8, 402.1, 402.2,
 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2,
 G2413.3.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved