2018-03-12 11:13:58 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 6TH EDITION (2017). |
| |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| ISSUANCE. |
| |
| |
| |
| |
| 1- ENERGY CALCULATIONS SUBMITTED PRESCRIPTIVE FORM |
| R402-2017 SUBMITTED; |
| A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM AS |
| REQUIRED BY GENERAL INSTRUCTIONS NOTE#4 OF FORM |
| SUBMITTED AND SEC. R103.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| B) ITEM #10B DOESN'T COMPLY WITH GENERAL INSTRUCTIONS |
| NOTE #1. NEED TO COMPLY WITH ALL THE REQUIREMENTS OF |
| TABLE R402A WHEN USING THE PRESCRIPTIVE METHOD. NEED |
| R-30 CEILING INSULATION OR USE PERFORMANCE METHOD FORM |
| 405-2017. |
| NOTE: ENGINEER WROTE DOWN SEC. R405.2.1. THIS ONLY |
| APPLIES WHEN USING PERFORMANCE METHOD FORM R405-2017. |
| |
| C) COMPLETE TABLE R402B AS REQUIRED BY GENERAL |
| INSTRUCTIONS NOTE#3. SEC. R101.5.1.1.1 FBC-ENERGY |
| CONSERVATION. |
| |
| D) ENGINEER OF RECORD PREPARING THE ENERGY CALCULATIONS |
| SUBMITTED TO PROVIDE HIS INFORMATION AS REQUIRED BY |
| CHAPTER 471 F. S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC |
| RECORDS. |
| |
| 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW BASED ON ALL THE SCOPE OF WORK SHOWN ON PLANS. |
| VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S |
| OVERHEAD AND PROFIT AND ALL DESIGN PROFESSIONAL FEES AS |
| REQUIRED BY SEC. 109.3 CITY AMENDMENTS. REVISE |
| VALUATION AS REQUIRED AND INCLUDE THE DESIGN |
| PROFESSIONAL FEES. |
| REPEAT COMMENT. |
| |
| |
| NOTE: |
| PLANS SUBMITTED ARE MISSING ONE MECHANICAL DRAWING M-1. |
| |
| |
| |