Notes
Date Text
2018-01-26 13:24:24JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 SMOKE ALARMS REQUIRED, AND SHALL BE ON ARC FAULT
 CIRCUIT.
 PROVIDE SMOKE ALARM ON EACH STORY OF THE DWELLING. FBC
 R314.3
 PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER
 CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 R314.3, FBC 107.2.1
  
 PROVIDE GFCI PROTECTED OUTLET ON 2ND FLOOR BALCONIES.
 NEC 210.52(E)(3); FBC RE3901.7
  
 WASHING MACHINE MAY HAVE TO BE ON GFCI IF WITHIN 6" OF
 THE SINK.