Plan Review Notes For Permit 18010190 |
Permit Number |
18010190 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-01-26 13:24:24 | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | SMOKE ALARMS REQUIRED, AND SHALL BE ON ARC FAULT | | CIRCUIT. | | PROVIDE SMOKE ALARM ON EACH STORY OF THE DWELLING. FBC | | R314.3 | | PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER | | CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE | | EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC | | R314.3, FBC 107.2.1 | | | | PROVIDE GFCI PROTECTED OUTLET ON 2ND FLOOR BALCONIES. | | NEC 210.52(E)(3); FBC RE3901.7 | | | | WASHING MACHINE MAY HAVE TO BE ON GFCI IF WITHIN 6" OF | | THE SINK. |
|