2018-01-26 10:12:00RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC 6TH EDITION (2017).
  
 1- PROVIDE COMPLETE ENERGY CALCULATIONS (2 COPIES) AS
 REQUIRED BY SEC. R501.1 FBC-ENERGY CONSERVATION, 6TH
 EDITION (2017).
  
 2- PLANS TO SHOW INSULATION ON WALLS AND CEILINGS AS
 REQUIRED BY SEC. R103.2 FBC-ENERGY CONSERVATION. NOTE:
 COORDINATE WITH ITEM #1 ABOVE TO AVOID
 CONFLICTS/DELAYS.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW BASED ON ALL THE SCOPE OF WORK SHOWN ON PLANS.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND ALL DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. REVISE
 VALUATION AS REQUIRED AND INCLUDE THE DESIGN
 PROFESSIONAL FEES.
  
 4- SHEET A-1:
 A) THE CURRENT CODE IN EFFECT IS THE FBC 6TH EDITION
 (2017) NOT THE FBC 2014. REVISE INFORMATION BELOW THE
 LEGAL DESCRIPTION. CHAPTER 553 F.S.
  
 B) PROPERTY LEGAL DESCRIPTION SHOWN IS INCORRECT.
 REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 C) CLARIFY WHY THERE IS A NOTE UNDER THE SCOPE OF WORK
 STATING THAT "RECONSTRUCTION OF UNIT UNDER SEPARATE
 PERMIT"?. SEC. 107.2.1 CITY AMENDMENTS.
  
 D) CLARIFY WHAT THE LETTERS A,B AND C LOCATED NEXT TO
 EACH EXTERIOR DOOR STANDS FOR?. THERE IS NOT LEGEND.
 SEC. 107.2.1 CITY AMENDMENTS.
  