2018-02-14 16:05:33 | ****PLAN REVIEW COMMENTS**** |
| |
| ART LANGE BUILDING PLANS EXAMINER |
| |
| DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS STREET |
| WEST PALM BEACH, FL 33402 |
| |
| 561-805-6718 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2010 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE |
| 2017 6TH EDITION |
| |
| SECOND REVIEW: |
| |
| CODE CRITERIA |
| |
| 1. OK |
| |
| |
| 2. IMPACT FEES OK |
| |
| |
| |
| 3. PRODUCT APPROVALS PARTIALLY ADDRESSED. |
| |
| (A) OK A PRODUCT APPROVAL WAS SUBMITTED FOR A LAWSON |
| 3200 CASEMENT WINDOW. THIS WAS NOT SHOWN ON THE PLANS. |
| |
| (B) MISSING PAGE 3 THE MASONITE DOOR PRODUCT APPROVAL |
| SUBMITTED HAS A MAXIMUM FRAME HEIGHT OF 81.875 INCHES. |
| THE PLANS SHOW AN 84 INCH DOOR. UPDATE AS NEEDED. |
| |
| (C) NOT PROVIDED PROVIDE ROOFING PRODUCT APPROVALS |
| ALONG WITH THE SELECTED ROOF ASSEMBLY USED. |
| |
| FBC 106.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| |
| 4. OK SIMPSON ATTACHMENT SHOWN AS LH 26 IS NOT FOUND. |
| DID YOU MEAN LU 26. |
| |
| NEW COMMENT: |
| |
| IF YOU WISH TO HAVE THE PERMIT ISSUED WITHOUT THE ABOVE |
| PRODUCT APPROVALS, ALTERNATIVELY YOU CAN SUBMIT THESE |
| LATER AS A DEFERRED SUBMITTAL BY LISTING THEM ON THE |
| PLANS AS DEFERRED SUBMITTALS. |
| |
| FBC 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| |
| |
| |
| WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| |
| HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 |
| 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| THE PERMIT PACKAGE. |
| |
| A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| |