Plan Review Notes
Plan Review Notes For Permit 18010142
Permit Number 18010142
Review Stop E
Sequence Number 1
Notes
Date Text
2018-01-22 13:48:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE 1 OF ELECTRICAL NOTES SPECIFIES USING THE 2011
 NEC, WHICH IS NOT THE CURRENT CODE. PROVIDE CORRECTION.
 FBC PREFACE
 2. NOTE 7 OF ELECTRICAL NOTES SPECIFIES THAT BEDROOM
 CIRCUITS SHALL HAVE "ARC PROTECTION". PER CODE: "BRANCH
 CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED." PROVIDE CORRECTION. NEC
 210.12; FBC RE E3902.16
 3. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; FBC 107.2.1
 4. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE
 E3706.2, E3902
 5. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 6. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B),
 FBC RE E3903.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  