2018-01-17 16:19:55 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #18010097 | | 1/17/18 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) REVISE THE EQUIPMENT SCHEDULE SHEET M2.0 TO SHOW THE | | CHANGE FROM THE JOHNSON CONTROLS 20-TON SYSTEM TO THE | | YORK SYSTEM. PLEASE NOTE THAT THE ENERGY CALCULATIONS | | MAY HAVE TO BE REVISED TO SHOW THE CHANGE IN EFFICIENCY | | RATING. | | | | 2) REFER TO TABLE 1509.6.5 FBC-14 BUILDING AND PROVIDE | | THE CLEARANCE DISTANCE BETWEEN THE FINISHED ROOF AND | | THE BOTTOM OF THE UNIT. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|