2020-02-27 07:10:34 | PLUMBING 2ND REVIEW**DENIED**17121018*8 |
| ONLY 7 OF THE 16 PLUMBING COMMENTS HAVE BEEN ADDRESSED |
| DURING THIS 2ND PLAN SUBMITTAL. IF THESE REMAINING 9 |
| COMMENTS ARE NOT COMPLETELY ADDRESSED A 4X PLAN REVIEW |
| FEE COULD BE ASSESSED PER FL STATE STATUTE |
| 553.80?ENFORCEMENT.?2(B)?WITH RESPECT TO EVALUATION OF |
| DESIGN PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT |
| FINDS IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH |
| THE FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT |
| DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE |
| TIMES FOR FAILURE TO CORRECT A CODE VIOLATION |
| SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, |
| INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, |
| STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, |
| VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS |
| SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF |
| THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO |
| CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH |
| TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED |
| FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT |
| OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS |
| REVIEW. |
| |
| COMMENTS STILL OUTSTANDING: |
| 1) PROVIDE COMPLETE INSTALLATION MANUAL/ SPECS FOR THE |
| GREASE INTERCEPTOR, DOMESTIC BOOSTER PUMPS, AND WATER |
| HEATERS. FBC 107.2.1 |
| 2) SHT. P1.01 WATER HEATER CALLS OUT BTU RATING AS 700K |
| BTU BUT UNDER HEATER DETAIL LIST THEN AS 800K BTU WHILE |
| SHT. P11 SAYS NO GAS ON THIS PROJECT. PLEASE CLARIFY |
| FBC 107.2.1 |
| 3) PROVIDE ANTI-SIPHONING BACKFLOW DEVICE FOR THE HOT |
| WATER STORAGE TANKS SHOWN ON SHT. P1.01. FBC-PLB 608.2 |
| 4) PROVIDE MEANS OF THERMO EXPANSION FOR THE HOT WATER |
| SYSTEM. FBC-PLB 607.3 |
| 5) SHT. L1-1 LIST THE BACKFLOW FOR THE IRRIGATION |
| SYSTEM A WILKINS 720A PVB. THIS WILKINS DEVICE IS NOT |
| LEAD FREE/ NS61 APPROVED OR RPZ. PVB?S ARE NOT |
| PERMITTED ON COMMERCIAL PROPERTIES WHILE BEING CONNECT |
| TO AN INDEPENDENT WATER METER. WPB CROSS CONNECTION |
| MANUAL 2017 |
| 6) PROVIDE A COMPLETE SANITARY, DOMESTIC WATER, STORM |
| WATER, AND GREASE WASTE ISOMETRIC DRAWING FROM THE |
| GROUND FLOOR TO THE 4TH. FBC 107.3.5 |
| 7) PROVIDE HOW YOU SIZED THE GREASE INTERCEPTOR AND |
| WHICH METHOD YOU ARE USING. FBC-PLB 1003 |
| 8) SHT. P1.00 SHOWS THE KITCHEN DISCHARGING INTO THE |
| SANITARY SEWER AND NOT THE GREASE. BEING THAT COOKING |
| WILL BE DONE HERE IT MUST GO THOUGH THE GREASE |
| INTERCEPTOR. FBC-PLB 1003.1 |
| 9) PROVIDE DETAIL ON ELEVATOR SUMP PUMP IS CONNECTING |
| INTO THE SANITARY SYSTEM. FBC 107.3.5 |
| |
| NEW COMMENTS BASE ON NEW SHEETS SUBMITTED: |
| 10) YOU CALL OUT TO SEE OWNERS RESPONSE LETTER BUT ONE |
| COULD NOT BE LOCATED IN RESPONSE #1. PLEASE PROVIDE. |
| PLEASE REMOVE THE WORDING EXTENDED STAY ROOMS AS THIS |
| THE TERM USED FOR STAYS OR 30 DAYS. FBC 107.2.1 |
| 11) IN YOUR RESPONSE LETTER IT JUMPS FROM 5 TO 7 AND 6 |
| IS MISSING. PLEASE CLARIFY. FBC 107.2.1 |
| 12) SHT. A 7.02 DETAIL #7 THE TOILET PAPER HOLDER PER |
| FBC-ACC 604.7 MUST BE 7?-9? FROM THE FRONT LIP OF THE |
| TOILET TO THE CENTER OF WHERE IT DISPENSES PAPER FROM. |
| 13) THE ACCESSIBLE WASHER AND DRYERS AS SHOWN I DO NOT |
| FEEL COMPLY. BEING A STACKABLE UNIT IT WOULD NOT MEET |
| THE REQUIRED REACH RANGES. THE PARALLEL CLEAR FLOOR |
| SPACE ACCESS TO THE UNITS IS BEING BLOCKED BY THE |
| CLOSET WALLS.PLEASE CLARIFY AND SHOW DETAIL SHOWING HOW |
| THIS DESIGN COMPLIES. FBC-ACC 611.2, 611.4 |
| 14) SHT A 7.02 DETAIL # 11. THE SHOWER PAN DETAIL IS |
| MISSING THE REQUIRED 2% PRE-PITCH UNDER THE PAN. |
| FBC-PLB 717.5.2 |
| 15) SHT. A 7.02 DETAIL # 7 PLEASE SHOW THE GRAB BAR IS |
| MOUNTED 12? FROM THE TOILET CENTERLINE TOWARDS THE WALL |
| AS SHOWN IN FBC-ACC 604.5.2 |
| 16) SHT. 7.02 DETAIL 8 THE ACCESSIBLE SHOWERS ARE SHOWN |
| WITH A CURB. THE MAX ALLOWED THRESHOLD IS ??FBC-ACC |
| 608.7 |
| |
| TIM HUNT |
| PLUMBING PLAN REVIEW |
| CITY OF WEST PALM BEACH (CGA SOLUTIONS) |
| 561-248-2703 |
| [email protected] |
| |
| |