2020-01-08 17:03:31GAS 2ND REVIEW**DENIED*17121018*NO RESPONSE WAS
 PROVIDED IN REGARD TO THE GAS COMMENTS. A GAS PLAN HAS
 NOT BEEN INCLUDED IN THIS SUBMITTAL PACKAGE. A GAS PLAN
 REVIEW HAS NOT BEEN PERFORMED AT THIS TIME. A SEPARATE
 GAS PERMIT IS REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS THAT REFLECT THE
 ENTIRE SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC
 SEC.107.2.1.
  
 1) GAS WATER HEATER IS LISTED AS 700K BTU BUT NOTE ON
 SHT. P11 SAYS NO GAS SYSTEMS FOR THIS PROJECT. PLEASE
 CLARIFY. WPB AMEND TO FBC 107.2.1
 2) IS THE GENERATOR, LINEN DRYER, OR ANY KITCHEN
 EQUIPMENT GAS. FBC 107.3.5
  
  
  
 TIM HUNT
 PLUMBING PLAN REVIEW
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 561-248-2703
 [email protected]
  
  
  