2020-01-13 12:54:42 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET A 2.01, A 5.00 & FP 2.00 - THERE APPEARS TO BE |
| AN OPEN RAILING ALONG THE MEZZANINE LEVEL CREATING AN |
| ATRIUM WITH NO PROTECTION. |
| |
| PER NFPA 101, CH 8 |
| |
| 8.6.7* ATRIUMS. UNLESS PROHIBITED BY CHAPTERS 11 |
| THROUGH 43, AN |
| ATRIUM SHALL BE PERMITTED, PROVIDED THAT ALL OF THE |
| FOLLOWING |
| CONDITIONS ARE MET: |
| |
| (1) THE ATRIUM IS SEPARATED FROM THE ADJACENT SPACES BY |
| FIRE |
| BARRIERS WITH NOT LESS THAN A 1-HOUR FIRE RESISTANCE |
| RATING, |
| WITH OPENING PROTECTIVES FOR CORRIDOR WALLS, UNLESS ONE |
| OF THE |
| FOLLOWING IS MET: |
| (A) THE REQUIREMENT OF 8.6.7(1) SHALL NOT APPLY TO |
| EXISTING, |
| PREVIOUSLY APPROVED ATRIUMS. |
| (B) ANY NUMBER OF LEVELS OF THE BUILDING SHALL BE |
| PERMITTED |
| TO OPEN DIRECTLY TO THE ATRIUM WITHOUT ENCLOSURE, BASED |
| ON THE RESULTS OF THE ENGINEERING ANALYSIS REQUIRED IN |
| 8.6.7(5). |
| (C)* GLASS WALLS AND INOPERABLE WINDOWS SHALL BE |
| PERMITTED |
| IN LIEU OF THE FIRE BARRIERS WHERE ALL THE FOLLOWING |
| ARE |
| MET: |
| I. AUTOMATIC SPRINKLERS ARE SPACED ALONG BOTH SIDES |
| OF THE GLASS WALL AND THE INOPERABLE WINDOWS AT |
| INTERVALS NOT TO EXCEED 6 FT (1830 MM). |
| II. THE AUTOMATIC SPRINKLERS SPECIFIED IN 8.6.7(C)I ARE |
| LOCATED AT A DISTANCE FROM THE GLASS WALL NOT TO |
| EXCEED 12 IN. (305 MM) AND ARRANGED SO THAT THE |
| ENTIRE SURFACE OF THE GLASS IS WET UPON OPERATION OF |
| THE SPRINKLERS. |
| III. THE GLASS WALL IS OF TEMPERED, WIRED, OR LAMINATED |
| GLASS HELD IN PLACE BY A GASKET SYSTEM THAT ALLOWS |
| THE GLASS FRAMING SYSTEM TO DEFLECT WITHOUT |
| BREAKING (LOADING) THE GLASS BEFORE THE SPRINKLERS |
| OPERATE. |
| IV. THE AUTOMATIC SPRINKLERS REQUIRED BY 8.6.7(C)I ARE |
| NOT REQUIRED ON THE ATRIUM SIDE OF THE GLASS WALL |
| AND THE INOPERABLE WINDOW WHERE THERE IS NO |
| WALKWAY OR OTHER FLOOR AREA ON THE ATRIUM SIDE ABOVE |
| THE MAIN FLOOR LEVEL. |
| V. DOORS IN THE GLASS WALLS OF GLASS OR OTHER MATERILA |
| THAT RESISTS PASSAGE OF SMOKE. |
| VI. DOORS IN THE GLASS WALLS ARE SELF-CLOSING OR |
| AUTOMATIC-CLOSING UPON DETECTION OF SMOKE. |
| VII. THE GLASS IS CONTINUOUS VERTICALLY, WITHOUT |
| HORIZONTAL MULLIONS, WINDOW TREATMENTS, OR OTHER |
| OBSTRUCTIONS THAT WOULD INTERFERE WITH THE WETTING |
| OF THE ENTIRE GLASS SURFACE. |
| (2) ACCESS TO EXITS IS PERMITTED TO BE WITHIN THE |
| ATRIUM, AND EXIT |
| DISCHARGE IN ACCORDANCE WITH 7.7.2 IS PERMITTED TO BE |
| WITHIN |
| THE ATRIUM. |
| (3) THE OCCUPANCY WITHIN THE ATRIUM MEETS THE |
| SPECIFICATIONS FOR |
| CLASSIFICATION AS LOW OR ORDINARY HAZARD CONTENTS. (SEE |
| 6.2.2.) |
| (4) THE ENTIRE BUILDING IS PROTECTED THROUGHOUT BY AN |
| APPROVED, |
| SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| WITH |
| SECTION 9.7 |
| (5) *FOR OTHER THAN EXISTING, PREVIOUSLY APPROVED |
| ATRIUMS, AN |
| ENGINEERING ANALYSIS IS PERFORMED THAT DEMONSTRATES |
| THAT THE |
| BUILDING IS DESIGNED TO KEEP THE SMOKE LAYER INTERFACE |
| ABOVE THE |
| HIGHEST UNPROTECTED OPENING TO ADJOINING SPACES, OR 6 |
| FT (1830 |
| MM) ABOVE THE HIGHEST FLOOR LEVEL OF EXIT ACCESS OPEN |
| TO THE |
| ATRIUM, FOR A PERIOD EQUAL TO 1.5 TIMES THE CALCULATED |
| EGRESS TIME |
| OR 20 MINUTES, WHICHEVER IS GREATER. |
| (6) *FOR OTHER THAN EXISTING, PREVIOUSLY APPROVED SMOKE |
| CONTROL |
| SYSTEMS, WHERE AN ENGINEERED SMOKE CONTROL SYSTEM IS |
| INSTALLED TO MEET THE REQUIREMENTS OF 8.6.7, THE SYSTEM |
| IS |
| INDEPENDENTLY ACTIVATED BY EACH OF THE FOLLOWING: |
| (A) UPON ACTUATION OF THE REQUIRED AUTOMATIC SPRINKLER |
| SYSTEM |
| WITHIN THE ATRIUM OR AREAS OPEN TO THE ATRIUM |
| (B) MANUAL CONTROLS THAT ARE READILY ACCESSIBLE TO THE |
| FIRE |
| DEPARTMENT |
| |
| PLEASE PROVIDE DETAILS IN COMPLIANCE WITH CODE. |
| |
| |
| |
| 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |