Date |
Text |
2020-01-03 09:44:25 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2014 |
| 5TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| NO ELECTRICAL RESPONSE PROVIDED. NO NEW ELECTRICAL |
| SUBMISSIONS FOR THIS REVIEW. ALL COMMENTS BELOW ARE |
| FROM FIRST REVIEW. |
| |
| 1. LABELING OF MAINS IS NOT CONSISTENT THROUGHOUT PLAN. |
| THERE APPEARS TO BE A SERVICE TO THE FIRE PUMP, WHICH |
| SHOULD BE LABELED AS AN ADDITIONAL SERVICE. THERE |
| APPEARS TO BE AN EMERGENCY SERVICE TO THE GENERATOR |
| ROOM, BUT THIS IS NOT LABLED AS AN ADDITIONAL SERVICE |
| AS REQUIRED. PANEL E IN THE MAIN ELECTRICAL ROOM IS NOT |
| ONE OF THE MAINS FOR SERVICE #1, AS THIS PANEL IS FED |
| FROM THE EMERGNECY SERVICE LOCATED IN THE GENERATOR |
| ROOM. PROVIDE CORRECTIONS AS NEEDED FOR CLARTY. WPB FBC |
| 107.2.1; NEC 230.2, 230.72(B) |
| 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 |
| 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| 4. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: |
| 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE |
| AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL |
| 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE |
| OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR |
| PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS, |
| CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE |
| 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR |
| FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC |
| EC 405.7.1 |
| 5. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED |
| IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE |
| AUTOMATIC CONTROL REQUIRED. FBC EC 405.2 |
| 6. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC 405.4.2 |
| 7. PROVIDE VOLTAGE DROP CALCULATIONS AS REQUIRED TO |
| MEET CODE. FBC EC C405.6.3 |
| 8. PROVIDE BLOCK NOTE SHOWING COMPLIANCE FOR COMPLETION |
| DOCUMENTS. FBC EC C405.6.4 |
| 9. SHEET E-1.12 SHOWS THE ELECTRICAL ROOMS ON FLOORS 2 |
| THROUGH 6 FOR THE "EXTENDED SUITES" HAVING A MAIN RATED |
| AS 1000 AMP, WHILE THE RISER DIAGRAM SHOWS THESE MAINS |
| AS 600 AMP. PROVIDE CLARIFICATION AND/OR CORRECTIONS. |
| IF THE MAINS ARE 800 AMPS OR ABOVE, PROVIDE THE PROPER |
| DOOR SWING AND HARDWARE PER NEC 110.26. ADDITIONALLY, |
| IT APPEARS THAT THE DIAGRAM FOR THE 3RD AND 4TH FLOOR |
| WAS REPEATED AND THERE IS NO DIAGRAM FOR FLOORS 5 AND |
| 6. PROVIDE CORRECTIONS. WPB FBC 107.2.1 |
| 10. NOTE ON RISER DIAGRAM SHOWS THE GENERATOR AS A |
| SEPARATELY DERIVED SYSTEM. HOWEVER, THE ATS IS SHOWN AS |
| A 3 POLE SWITCH, WHICH WOULD NOT BE A SEPARATELY |
| DERIVED SYSTEM. PROVIDE CLARIFICATION AND CORRECTIONS |
| AS NEEDED. WPB FBC 107.2.1; NEC 250.30 |
| 11. THE ATS IS THE GENERATOR ROOM APPEARS TO BE AN |
| ADDITIONAL SERVICE FOR EMERGNECY SYSTEMS, BUT IS NOT |
| LABELED AS SUCH. PROVIDE CORRECTIONS TO LABELING AND |
| GROUNDING OF THIS SERVICE PER CODE. NEC 230.2, 250.24, |
| 250.28, 250.30, 250.32, 250.35, 250.50 |
| 12. PLAN SUBMISSION INCLUDES TWO SHEETS MARKED E-1.09 |
| AND THEY EACH HAVE DIFFERENT INFORMATION ON THEM. |
| PROVIDE CORRECTION. WPB FBC 107.2.1 |
| 13. PROVIDE EVIDENCE OF COMPLIANCE WITH NEC 240.87. |
| 14. THERE ARE SEVERAL PANELS THAT HAVE THE SAME |
| IDENTIFICATION THROUGHOUT THE SYSTEM. EACH PANEL SHOULD |
| HAVE A DISTINCT IDENTIFICATION FOR CLARITY. PROVIDE |
| CORRECTION AND PANEL SCHEDULES TO CORRESPOND. NEC |
| 210.19, 215.2, 215.5, 408.4 |
| 15. PROVIDE ACCURATE LOAD CALCULATION FOR EACH SERVICE |
| AND THE CORRESPONDING MAINS TO MATCH THE INFORMATION |
| PROVIDED ON THE RISER DIAGRAM. THERE ARE DISCREPANCIES |
| FOR THE LABELING OF MAINS AND THE LOADS THEY FEED. NEC |
| 220; WPB FBC 107.2.1 |
| 16. LOAD CALCULATION PROVIDED FOR "EXTENDED SUITES" |
| STATES THAT IT IS BASED ON NEC 220.32, WHICH DOES NOT |
| EXIST. PROVIDE CLARIFICATION AND CORRECTIONS. WPB FBC |
| 107.2.1 |
| 17. RISER DIAGRAM SHOWS THE GENERATOR FEEDING A GUTTER |
| THAT THEN FEEDS TWO DISCONNECTS, ONE FOR FIRE PUMP, AND |
| ONE FOR ATS THAT FEEDS PANEL E. THE DESIGN AS SHOWN IN |
| NOT CODE COMPLIANT, AS FIRE PUMP WIRING IS REQUIRED TO |
| REMAIN INDEPENDENT OF ALL OTHER WIRING. PROVIDE |
| CORRECTION. NEC 659.6(A)(2), 445.18 |
| 18. IF AN ADDITIONAL DISCONNECT FOR FIRE PUMP IS TO BE |
| INSTALLED AS PERMITTED IN NEC 695.4, THIS DISCONNECT |
| MUST BE SUPERVISED PER ONE OF THE METHODS STIPULATED IN |
| THE CODE. PROVIDE DETAIL ON PLAN FOR METHOD OF |
| SUPERVISION. NEC 695.4(B)(3)(E) |
| 19. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC |
| 105.1, 107.2.1 |
| 20. PROVIDE DETAILS OF EQIPMENT ENCLOSURES USED IN POOL |
| ROOM FOR ANY ELECTRICAL EQUIPMENT. NEC TABLE 110.28 |
| 21. VENDING MACHINES REQUIRE READILY ACCESSIBLE GFCI |
| PROTECTION. PROVIDE CORRECTION. NEC 422.51 |
| 22. SHEETS E.107, E.108, AND E.109, PROVIDE GFCI |
| PROTECTION FOR ALL RECEPTACLES LOCATED IN BATHROOMS. |
| NEC 210.8 |
| 23. SHEETS CONTAINING DETAILS OF HOTEL ROOMS AND |
| EXTENDED SUITES HAVE SEVERAL NOTES IN PARENTHESES THAT |
| ARE NOT EXPLAINED OR DETAILED. PROVIDE CORRECTION. WPB |
| FBC 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |