Date |
Text |
2020-01-10 18:33:57 | PLAN REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) NOT ADDRESSED. NO RESPONSE TO COMMENT. ART IN PUBLIC |
| PLACES |
| THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES |
| ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR |
| NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT |
| APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL |
| PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. |
| PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| PROJECT CONSTRUCTION COST. |
| PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| PROJECTS. |
| SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE |
| DEVELOPMENT. |
| (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND |
| THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL |
| PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW |
| CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN |
| EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE |
| EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS |
| WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED |
| CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES |
| REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED |
| SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF |
| THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW |
| CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS. |
| FOR INFORMATION PLEASE CONTACT: |
| MS. SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR AT |
| 822-1515 OR E-MAIL: [email protected] |
| |
| 2) NOT ADDRESSED. NO RESPONSE TO COMMENT. THIS BUILDING |
| QUALIFIES AS A THRESHOLD BUILDING AND IS REQUIRED TO |
| COMPLY WITH THE FOLLOWING: |
| THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD |
| BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| PERSONS. |
| |
| A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION |
| PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| WITH THE PERMITTED DOCUMENTS. |
| |
| B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) |
| FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY |
| THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED |
| TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED |
| AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED |
| BEFORE PERMIT ISSUANCE WILL TAKE PLACE. |
| |
| C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT |
| 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED |
| TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS |
| AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. |
| |
| D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF |
| INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME |
| MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNATE WILL |
| REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN |
| INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| |
| E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| FOR THIS TYPE OF CONSTRUCTION. |
| |
| F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| IN BLACK & WHITE. |
| |
| G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| DOCUMENTS BY THE CONTRACTOR. |
| |
| H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL |
| BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| |
| I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR |
| THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS |
| REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, |
| APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND |
| CEILINGS. |
| |
| J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL |
| BE HAPPY TO SEND YOU A COPY OF THE OCTOBER 2018 |
| GUIDELINES AND POLICIES FOR PROJECTS CONCERNING |
| THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS. |
| |
| 3) NO RESPONSE TO COMMENT. 109.3 BUILDING PERMIT |
| VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| EACH PERMIT. |
| |
| ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| REMAINING BALANCE WILL EFFECTIVELY BE THE VALUE OF THE |
| BUILDING THAT THE PERMIT FEES WILL BE BASED ON FOR THIS |
| PERMIT. THE BUILDING DEPARTMENT DOES NOT WANT TO |
| COLLECT TWICE FOR THE VALUE OF THESE SUB-PERMITS NOT |
| COVERED UNDER THE PRIME OR MASTER PERMIT. |
| |
| 4) NOT ADDRESSED. NO RESPONSE TO COMMENT. PROVIDE A PER |
| FLOOR AREA BREAKDOWN FOR EACH OCCUPANCY TYPE ON THAT |
| FLOOR. THIS IS REQUIRED IN ORDER TO DO AN ACCURATE |
| VALUATION AMOUNT FOR THE BUILDING. FBC 109.3 |
| |
| 5) NOT ADDRESSED. NO RESPONSE TO COMMENT. THE |
| STRUCTURAL DRAWINGS HAVE NOT BEEN SIGNED AND SEALED BY |
| THE DESIGN PROFESSIONAL OF RECORD AS REQUIRED BY FS 471 |
| OR FS 481 AND ARE MARKED "NOT FOR CONSTRUCTION". |
| |
| 6) NOT ADDRESSED. THE ARCHITECT'S RESPONSE LETTER |
| REFERS TO AN OWNER'S RESPONSE LETTER WHICH WAS NOT |
| FOUND IN NOT ADDRESSED. THE CONSTRUCTION DOCUMENTS. |
| SPECIFY ON THE PLANS THAT THE EXTENDED STAY ROOMS WILL |
| NOT BE RENTED OR LEASED TO THE SAME OCCUPANT FOR MORE |
| THAN THIRTY DAYS. THE CODE ANALYSIS ON SHEET A-1.00A, |
| SPECIFIES THE HOTEL AND EXTENDED STAY ROOMS AS |
| OCCUPANCY GROUP AS R-1. THE EXTENDED STAY ROOMS PROVIDE |
| COMPLETE INDEPENDENT LIVING FACILITIES INCLUDING |
| PERMANENT PROVISIONS FOR COOKING AND MEET THE |
| DEFINITION OF A DWELLING UNIT IN CHAPTER 2 OF THE |
| BUILDING CODE. WILL THE EXTENDED STAY ROOMS BE RENTED |
| OR LEASED TO THE SAME OCCUPANT FOR MORE THAN 30 DAYS? |
| IF SO, THEY ARE CLASSIFIED AS HOTEL (NON-TRANSIENT) AND |
| GROUP R-2. THIS WILL REQUIRE THESE ROOMS TO TO COMPLY |
| WITH FAIR HOUSING GUIDELINES. FBC SECTION 310 |
| |
| 7) NOT ADDRESSED. NO RESPONSE TO COMMENT. SUBMIT THE |
| APPROPRIATE FORMS TO SHOW COMPLIANCE WITH THE SECTION |
| C401.2 OF THE 2014 FBC ENERGY CONSERVATION. |
| |
| 8) NOT ADDRESSED. NO RESPONSE TO COMMENT. SUBMIT A |
| GEOTECHNICAL (SOIL INVESTIGATION) REPORT FOR THE |
| PROJECT. FBC 1803 |
| |
| 9) COMPLIED. |
| |
| 10) COMPLIED. |
| |
| 11) COMPLIED. |
| |
| 12) COMPLIED. |
| |
| 13) COMPLIED. |
| |
| 14) COMPLIED. |
| |
| 15) NOT COMPLETELY ADDRESSED. IT DOES NOT APPEAR THAT |
| THE ROOMS ARE ADEQUATELY DISPERSED AS REQUIRED BY FBC |
| ACCESSIBILITY SECTION 224.5 WITH REGARD TO LOCATION AND |
| VIEWS. THE FBC ACCESSIBILITY TABLE 224.4 REQUIRES 17 |
| GUEST ROOMS WITH COMMUNICATION FEATURES. SECTION 224.5 |
| DISPERSION REQUIRES AT LEAST ONE GUEST ROOM REQUIRED TO |
| PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL |
| ALSO PROVIDE COMMUNICATION FEATURES COMPLYING WITH |
| 806.3. NOT MORE THAN 10 PERCENT OF GUEST ROOMS REQUIRED |
| TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL |
| BE USED TO SATISFY THE MINIMUM NUMBER OF GUEST ROOMS |
| REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING |
| WITH 806.3. TEN PERCENT OF THE 10 REQUIRED GUEST ROOMS |
| WITH MOBILITY FEATURES IS ONE (1). THEREFORE, ONLY ONE |
| OF THE REQUIRED 17 GUEST ROOMS WITH COMMUNICATION |
| FEATURES CAN BE A GUEST ROOM WITH MOBILITY FEATURES. |
| PLEASE REVISE PLANS TO COMPLY. |
| |
| 16) COMPLIED. |
| |
| 17) NOT ADDRESSED. NO RESPONSE TO COMMENT. SPECIFY THE |
| LIVE LOADS REQUIRED BY FBC TABLE 1607.1 FOR EACH AREA |
| OF THE BUILDING ON THE PLANS. |
| |
| 18) NOT CORRECTLY ADDRESSED. THE OPENING CALCULATIONS |
| ON SHEET A-1.00A DO NOT USE THE ENTIRE PERIMETER WALL |
| AREA OR THE TOTAL PERIMETER LENGTH OF ALL FOUR SIDES OF |
| EACH TIER OF THE PARKING GARAGE AS REQUIRED BY FBC |
| 406.5. THE PLANS SPECIFY THAT THE PARKING GARAGE IN |
| THIS BUILDING IS AN OPEN GARAGE. THIS DOES NOT APPEAR |
| TO BE AN OPEN GARAGE. THE OPENINGS DO NOT MEET THE |
| REQUIREMENT OF FBC 406.5.2 FOR BEING UNIFORMLY |
| DISTRIBUTED ON AT LEAST TWO SIDES OF THE STRUCTURE. THE |
| CALCULATIONS FOR THE AREA OF OPENINGS IN THE EXTERIOR |
| WALLS APPEARS TO BE INCORRECT. FBC 406.5 REQUIRES THE |
| AREA OF SUCH OPENINGS IN EXTERIOR WALLS ON A TIER TO BE |
| NOT LESS THAN 20 PERCENT OF THE TOTAL PERIMETER WALL |
| AREA OF EACH TIER. REVISE PLANS FOR AN ENCLOSED GARAGE. |
| |
| 19) COMPLIED. |
| |
| 20) NOT COMPLETELY ADDRESSED. NOT ALL OF THE REQUESTED |
| INFORMATION HAS BEEN PROVIDED. |
| THE LIFE SAFETY PLANS NEED TO SHOW THE FOLLOWING FOR |
| EACH FLOOR: |
| A) THE NUMBER OF OCCUPANTS IN EACH AREA FBC 1004.1 |
| B) THE CUMULATIVE OCCUPANT LOADS FBC 1004.1.1 |
| C) THE EXIT SEPARATION DISTANCE FBC 1015.2.1 |
| D) THE COMMON PATH OF EGRESS TRAVEL DISTANCE FBC 1014.3 |
| E) THE EXIT ACCESS TRAVEL DISTANCE FBC 1016.3 |
| F) THE CLEAR WIDTH OF THE EXIT OR EXIT ACCESS DOORS FBC |
| 1008.1.1 |
| G) THE CAPACITY OF EGRESS DOORS, OCCUPANT LOAD SERVED |
| AND MEANS OF EGRESS FACTOR FBC1005.3.2 |
| H) THE DISTRIBUTION OF EGRESS CAPACITY FBC1005.5 |
| |
| 21) COMPLIED. |
| |
| 22) NOT COMPLETELY ADDRESSED. THE LINEN AND TRASH CHUTE |
| DISCHARGE ROOMS HAVE TO BE IDENTIFIED AND SEPARATED ON |
| THE PLANS.FBC 713.13 THE LINEN CHUTE SECTION ON SHEET |
| A-6.02 HAS THE TERMINATION ROOM AND THE ACCESS ROOMS |
| LABELED AS GARBAGE ROOMS. PLEASE CORRECT. FBC 713.13.1 |
| |
| 23) COMPLIED. |
| |
| 24) COMPLIED. |
| |
| 25) COMPLIED. |
| |
| 26) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| CITY RE-SUBMITTAL FORM. |
| |
| NEW COMMENTS |
| |
| 27) SPECIFY THE EXIT SEPARATION DISTANCE FOR THE |
| RESTAURANT AREA LOCATED ON THE GROUND FLOOR. |
| |
| 28) SHOW THAT THE LOCATION OF THE EXERCISE MACHINES AND |
| EQUIPMENT IN THE GYM WILL COMPLY WITH THE REQUIREMENTS |
| OF 2014 FBC ACCESSIBILITY SECTIONS 236 AND 1004. |
| |
| 29) SHOW THAT THE BAR IN THE RESTAURANT COMPLIES WITH |
| 2014 FBC ACCESSIBILITY SECTIONS 226 AND 902. |
| |
| 30) SHOW THAT THE CHECK-IN ARE SERVICE COUNTER COMPLIES |
| WITH 2014 FBC ACCESSIBILITY SECTION 904. |
| |
| |
| |
| |