Plan Review Notes
Plan Review Notes For Permit 17121018
Permit Number 17121018
Review Stop P
Sequence Number 1
Notes
Date Text
2019-03-25 14:53:07PLUMBING 1ST REVIEW**DENIED**
  
  
 1)PLEASE PROVIDE WHICH SAFE HARBOR UNDER THE FAIR
 HOUSING ACT YOU INTENT TO USE AND SHOW ON PLANS.
 PROVIDE FLOOR PLAN SHOWING WHAT DESIGN SPEC EACH UNIT
 WILL BE. FBC 107.3.5
  
 2) SHT. A-2.13, 2.12, 3.00, AND 4.00 ARE MISSING THE
 REQUIRED CLEAR FLOOR SPACE FOR THE SHOWERS IN THE
 ACCESSIBILITY COMPLANT ROOMS. FBC 107.3.5
  
 3) SHT. A-2.13 PROVIDE CLEAR FLOOR SPACE AS REQUIRED IN
 FRONT OF THE WASHING MACHINE AND DRYER. ALSO INCLUDE
 REACH RANGES. FBC-ACC 611, 308
  
 4) SHT. A 2.14 PROVIDE MIRROR DETAIL SHOWING MAX 34" IS
 TO THE REFLECTIVE SURFACE. FBC-ACC 603.3
  
 5) SHT. A 2.14 PROVIDE DETAIL SHOWING SIDE GRAB BAR IS
 42" AND OVERALL WILL BE 54". FBC-ACC 604.5.1
  
 6) PROVIDE COMPLETE INSTALLATION MANUAL/ SPECS FOR THE
 GREASE INTERCEPTOR, DOMESTIC BOOSTER PUMPS, WATER
 HEATERS. FBC 107.2.1
  
 7) PROVIDE SHOWER PAN DETAIL. IF USING ANY OTHER
 PRODUCT THEN VINYL PAN LINER PROVIDE INSTALLATION
 MANUAL AND PRODUCT APPROVAL SHEETS. FBC 107.2.1
  
 8) SHT. A 7.02 DETAIL #8 SHOW THE HAND HELD SHOWER
 ABOVE 48". THE HAND HELD SHALL ME MOUNTED SO THAT THE
 GRABBING SURFACE IS MAX 48". FBC-ACC 608.5.3
  
 9) SHT. P1.01 WATER DETAIL LIST BTU'S AS 700,000 BUT
 DETAIL UNDER LIST THEM AS 800,000 BTU. PLEASE CLARIFY
 FBC 107.1
  
 10) PROVIDE ANTI-SIPHONING BACKFLOW DEVICE FOR THE HOT
 WATER STORAGE TANKS ON SHT. P1.01. FBC-PLB 608.2
  
 11) PROVIDE A MEANS OF THEMO EXPANSION FOR THE HOT
 WATER SYSTEM. FBC-PLB 607.3
  
 12) SHT. LI-1 LIST THE BACKFLOW FOR THE IRRAGATION
 SYSTEM AS A PVB WILKINS 720A. THE WILKINS DEVICE IS NOT
 NSF61 COMPLAINT AND PER THE CITY OF W.P.B CROSS
 CONNECTION MANUAL THE CITY WATER SYSTEM SHALL BE
 PROTECTED BY A RPZ LEAD FREE DEVICE.
  
 13) PROVIDE A COMPLETE SANITARY, DOMESTIC WATER, STORM
 WATER, AND GREASE WASTE ISOMETRIC DRAWING FROM THE
 GROUND FLOOR TO THE 4TH. FBC-PLB 107.3.5
  
 14) PROVIDE COMPLETE INSTALLATION MANUAL AND PROVIDE
 CALCULATIONS ON HOW YOU SIZED THE INTERCEPTORS. FBC-PLB
 1003, F.A.C 64E-6
  
 15) SHT. P-1.00 SHOWNS THE KITCHENETTE ON THE SEWER
 LINE. BEING THAT COOKING WILL BE PERFORMED THIS SINK
 SHALL DISCHARGE INTO THE GREASE SYSTEM. FBC-PLB 1003.1
  
 16) PROVIDE DETAIL SHOWING THE ELEVATOR SUMP WILL
 DISCHARGE INTO A INDIRECT WASTE INTO THE SANITARY SEWER
 SYSTEM. FBC 802.1.3
  
 **BEING THAT SEVERAL PAGES ARE MISSING FOR THE
 ISOMETRIC A COMPLETE AND THOROUGH REVIEW COULD NOT BE
 PERFORMED.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.**
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]