Plan Review Notes For Permit 17121018 |
Permit Number |
17121018 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-03-25 15:01:05 | GAS 1ST REVIEW**DENIED** | | | | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BEIS | | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. | | PROVIDE COMPLETE PLANS AND GAS RISER THAT REFLECTS THE | | ENTIRE SCOPE OF GAS WORK TO BE DONE. AT THIS TIME. WPB | | AMEND. TO FBC SEC. 107.2.1. | | | | 1) WATER HEATER ARE LISTED AS 700,000 BTU GAS BUT NOTE | | ON SHT. -P11 SAYS NO GAS SYSTEM ON THIS PROJECT. PEASE | | CLEARIFY | | | | 2) IS THE GENERATOR, LINEN DRYER, OR ANY KITCHEN | | EQUIPMENT GAS? FBC 107.3.5 | | | | | | | | PLEASE EMAIL ME AND REQUEST A COMPLETE GAS CHECK LIST | | OF WHAT IS REQUIRED TO SUBMIT A GAS PLAN. | | | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | CITY OF WEST PALM BEACH | | 561-248-2703 | | [email protected] | | | | | | | | |
|