Plan Review Notes
Plan Review Notes For Permit 17121018
Permit Number 17121018
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-03-04 10:56:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 2.01 - THERE IS AN INDICATION OF AN EMEGENCY
 GENERATOR. THE GENERATOR INSTALLATION SHALL BE UNDER
 SEPARATE SHOP DRAWINGS AND PERMIT.
  
 THE GENRATOR INSTALL SHALL ALSO COMPLY WITH THE
 REQUIRMENTS OF NFPA 110, TO INCLUDE TYPE
  
 PER NFPA 110
  
 CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY
 SYSTEMS (EPSSS)
 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF
 ELECTRICAL
 POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO
 LOADS FOR
 A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND
 WITHIN A SPECIFIED
 TIME FOLLOWING LOSS OR FAILURE OF THE NORMAL POWER
 SUPPLY
 AS SPECIFIED IN TABLE 4.1(B).
  
 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN
 HOURS, FOR
 WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD
 WITHOUT
 BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).]
 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN
 SECONDS,
 THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE
 TRANSFER
 SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE
 4.1(B)
 PROVIDES THE TYPES DEFINED BY THIS STANDARD.
 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF
 EQUIPMENT
 INSTALLATION, PERFORMANCE, AND MAINTENANCE.
 4.4.1* LEVEL 1 SYSTEMS SHALL BE INSTALLED WHERE FAILURE
 OF THE
 EQUIPMENT TO PERFORM COULD RESULT IN LOSS OF HUMAN LIFE
 OR
 SERIOUS INJURIES.
 4.4.2* LEVEL 2 SYSTEMS SHALL BE INSTALLED WHERE FAILURE
 OF THE
 EPSS TO PERFORM IS LESS CRITICAL TO HUMAN LIFE AND
 SAFETY.
 4.4.3 ALL EQUIPMENT SHALL BE PERMANENTLY INSTALLED.
 4.4.4* LEVEL 1 AND LEVEL 2 SYSTEMS SHALL ENSURE THAT
 ALL LOADS
 SERVED BY THE EPSS ARE SUPPLIED WITH ALTERNATE POWER
 THAT
 MEETS ALL THE FOLLOWING CRITERIA:
 (1) OF A QUALITY WITHIN THE OPERATING LIMITS OF THE
 LOAD
 (2) FOR A DURATION SPECIFIED FOR THE CLASS AS DEFINED
 IN TABLE
 4.1(A)
 (3) WITHIN THE TIME SPECIFIED FOR THE TYPE AS DEFINED
 IN TABLE
 4.1(B)
  
 PLEASE PROVIDE THE CLASSIFICATION, TYPE AND LEVEL ON
 THIS MASTER PLAN AND AN APPLICABLE NOTE FOR SHOP
 DRAWINGS.
  
  
 1A) SHEET M1.0A - THERE ARE NO FIRE CODE REFERENCES FOR
 REVIEW OR COMPLIANCE. THE INSTALLATION SHALL COMPLY
 WITH NFPA 110, STANDARD FOR
 EMERGENCY AND STANDBY POWER SYSTEMS, 2013 EDITION
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE ACKNOWLEDGMENT OF THE ABOVE CODE.
  
  
  
  
  
 2) SHEET A 2.01 - THE VENTILATION/EXHAUST SYSTEMS ARE
 INDCATED WITH OPENINGS THAT MAY IN CONFLICT WITH THE
 REQUIREMENTS PER ABOVE.
  
  
 7.7 HEATING, COOLING, AND VENTILATING.
 7.7.1* WITH THE EPS RUNNING AT RATED LOAD, VENTILATION
 AIRFLOW
 SHALL BE PROVIDED TO LIMIT THE MAXIMUM AIR TEMPERATURE
 IN THE
 EPS ROOM OR THE ENCLOSURE HOUSING THE UNIT TO THE
 MAXIMUM
 AMBIENT AIR TEMPERATURE REQUIRED BY THE EPS
 MANUFACTURER.
 7.7.1.1 CONSIDERATION SHALL BE GIVEN TO ALL THE HEAT
 EMITTED TO
 THE EPS EQUIPMENT ROOM BY THE ENERGY CONVERTER,
 UNINSULATED
 OR INSULATED EXHAUST PIPES, AND OTHER HEAT-PRODUCING
 EQUIPMENT.
 7.7.2 AIR SHALL BE SUPPLIED TO THE EPS EQUIPMENT FOR
 COMBUSTION.
 7.7.2.1* FOR EPS SUPPLYING LEVEL 1 EPSS, VENTILATION
 AIR SHALL
 BE SUPPLIED DIRECTLY FROM A SOURCE OUTSIDE THE BUILDING
 BY AN
 EXTERIOR WALL OPENING OR FROM A SOURCE OUTSIDE THE
 BUILDING BY
 A 2-HOUR FIRE-RATED AIR TRANSFER SYSTEM.
 7.7.2.2 FOR EPS SUPPLYING LEVEL 1 EPSS, DISCHARGE AIR
 SHALL BE
 DIRECTED OUTSIDE THE BUILDING BY AN EXTERIOR WALL
 OPENING OR TO
 AN EXTERIOR OPENING BY A 2-HOUR FIRE-RATED AIR TRANSFER
 SYSTEM.
 7.7.2.3 FIRE DAMPERS, SHUTTERS, OR OTHER SELF-CLOSING
 DEVICES SHALL
 NOT BE PERMITTED IN VENTILATION OPENINGS OR DUCTWORK
 FOR SUPPLY
 OR RETURN/DISCHARGE AIR TO EPS EQUIPMENT FOR LEVEL 1
 EPSS.
 7.7.3 VENTILATION AIR SUPPLY SHALL BE FROM OUTDOORS OR
 FROM A
 SOURCE OUTSIDE THE BUILDING BY AN EXTERIOR WALL OPENING
 OR
 FROM A SOURCE OUTSIDE THE BUILDING BY A 2-HOUR
 FIRE-RATED AIR
 TRANSFER SYSTEM.
 7.7.4 VENTILATION AIR SHALL BE PROVIDED TO SUPPLY AND
 DISCHARGE
 COOLING AIR FOR RADIATOR COOLING OF THE EPS WHEN
 RUNNING
 AT RATED LOAD.
 7.7.4.1 VENTILATION AIR SUPPLY AND DISCHARGE FOR
 RADIATORCOOLED
 EPS SHALL HAVE A MAXIMUM STATIC RESTRICTION OF 125 PA
 (0.5 IN. OF WATER COLUMN) IN THE DISCHARGE DUCT AT THE
 RADIATOR
 OUTLET.
 7.7.4.2 RADIATOR AIR DISCHARGE SHALL BE DUCTED OUTDOORS
 OR TO
 AN EXTERIOR OPENING BY A 2-HOUR RATED AIR TRANSFER
 SYSTEM.
 7.7.5 MOTOR-OPERATED DAMPERS, WHEN USED, SHALL BE
 SPRING
 OPERATED TO OPEN AND MOTOR CLOSED. FIRE DAMPERS,
 SHUTTERS, OR
 OTHER SELF-CLOSING DEVICES SHALL NOT BE PERMITTED IN
 VENTILATION
 OPENINGS OR DUCTWORK FOR SUPPLY OR RETURN/DISCHARGE AIR
 TO
 EPS EQUIPMENT FOR LEVEL 1 EPSS.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND OR CORRECT AS
 APPLICABLE.
  
  
  
 3) SHEET A 2.01 - THERE IS AN OVERHEAD DOOR INDICATED
 IN A 2 HOUR FIRE WALL AT THE STORAGE GARBAGGE ROOM.
  
 THERE IS NO FIRE RATING INDICATED ON THE DOOR SCHEDULE.
  
 ADDITIONALLY, WILL THIS DOOR BE ON A FUSIBLE LINK?
  
 PLEASE REVIEW AND CORRECT AND PROVIDE DETAILS.
  
  
  
  
 4) SHEET A 2.01 - THE EXITING FROM THE GENERATOR ROOM
 INDICATES PASSAGE ALONG A 2 HOUR WALL; HOWEVER, THERE
 IS A LOUVER INDICATED AT THAT WALL AREA.
  
 THE PATH OF TRAVEL IS REQUIRED TO BE PROTECTED PER NFPA
 101, CHAPTER 8 FEATURES OF FIRE PROTECTION
  
 8.3.1.2* FIRE BARRIERS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
 (1) THE FIRE BARRIERS ARE CONTINUOUS FROM OUTSIDE WALL
 TO OUTSIDE WALL
 OR FROM ONE FIRE BARRIER TO ANOTHER, OR A COMBINATION
 THEREOF,
 INCLUDING CONTINUITY THROUGH ALL CONCEALED SPACES, SUCH
 AS THOSE
 FOUND ABOVE A CEILING, INCLUDING INTERSTITIAL SPACES.
 (2) THE FIRE BARRIERS ARE CONTINUOUS FROM OUTSIDE WALL
 TO OUTSIDE WALL
 OR FROM ONE FIRE BARRIER TO ANOTHER, AND FROM THE FLOOR
 TO THE
 BOTTOM OF THE INTERSTITIAL SPACE, PROVIDED THAT THE
 CONSTRUCTION
 ASSEMBLY FORMING THE BOTTOM OF THE INTERSTITIAL SPACE
 HAS A FIRE
 RESISTANCE RATING NOT LESS THAN THAT OF THE FIRE
 BARRIER.
 8.3.1.3 WALLS USED AS FIRE BARRIERS SHALL COMPLY WITH
 CHAPTER 7 OF
 NFPA 221, STANDARD FOR HIGH CHALLENGE FIRE WALLS, FIRE
 WALLS, AND
 FIRE BARRIER WALLS. THE NFPA 221 LIMITATION ON
 PERCENTAGE WIDTH OF
 OPENINGS SHALL NOT APPLY.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES AND NARRATIVE.
  
  
  
 5) SHEET A 2.01 - THERE IS AN INDICATION OF A EXIT FROM
 THE GARAGE AREA PASSING BY A BOILER ROOM.
  
 28.3.2 PROTECTION FROM HAZARDS.
 28.3.2.1 GENERAL. ALL ROOMS CONTAINING HIGH-PRESSURE
 BOILERS,
 REFRIGERATING MACHINERY, TRANSFORMERS, OR OTHER SERVICE
 EQUIPMENT
 SUBJECT TO POSSIBLE EXPLOSION SHALL NOT BE LOCATED
 DIRECTLY UNDER OR
 DIRECTLY ADJACENT TO EXITS AND SHALL BE EFFECTIVELY CUT
 OFF FROM
 OTHER PARTS OF THE BUILDING AS SPECIFIED IN SECTION
 8.7.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES AND NARRATIVE
  
  
  
 6) SHEET A 9.0 - THERE IS AN INDICATION OF A FP&L VAULT
 BOX DIRECTLY BESIDE AN EXIT FROM STAIRWAY, ST 1.
  
 28.3.2 PROTECTION FROM HAZARDS.
 28.3.2.1 GENERAL. ALL ROOMS CONTAINING HIGH-PRESSURE
 BOILERS,
 REFRIGERATING MACHINERY, TRANSFORMERS, OR OTHER SERVICE
 EQUIPMENT
 SUBJECT TO POSSIBLE EXPLOSION SHALL NOT BE LOCATED
 DIRECTLY UNDER OR
 DIRECTLY ADJACENT TO EXITS AND SHALL BE EFFECTIVELY CUT
 OFF FROM
 OTHER PARTS OF THE BUILDING AS SPECIFIED IN SECTION
 8.7.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES AND NARRATIVE
  
  
  
  
 7) SHEET A 9.0 - THERE ARE DOORS THAT APPEAR TO OPEN
 AND ENCROACH MORE THAN ONE HALF THE REQUIRED EGRESS
 WIDTH; LUGGAGE ROOM, CONFERENCE SITTING AREA CORRIDOR
 (3), THE EXIT DOOR AT ST 4,
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 7.2.1.4.3* DOOR LEAF ENCROACHMENT.
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS
 SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED
 WIDTH OF AN AISLE,
 A CORRIDOR, A PASSAGEWAY, OR A LANDING UNOBSTRUCTED,
 UNLESS BOTH
 OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING
 BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
  
  
  
  
 8) SHEET A 2.01 & A 2.03 - THERE APPEARS TO BE STOVE
 TOPS INDICATED WITH THE KITCHENETTE AND BREAK ROOM.
  
 ANY KITCHEN EQUIPMENT WITHIN THESE ROOMS SHALL BE
 PROTECTED PER NFPA 101 & 96 WITH ALL APPLICABLE HOODS
 AND SUPPRESSION SYSTEMS UNDER SEPARATE SHOP DRAWINGS.
  
 PER NFPA 1 CH 50 & 101 CH 9:
  
 50.1.1 THE DESIGN, INSTALLATION, OPERATION, INSPECTION
 AND MAINTENANCE OF ALL PUBLIC AND PRIVATE COMMERCIAL
 COOKING
 EQUIPMENT SHALL COMPLY WITH THIS CHAPTER AND NFPA 96,
 STANDARD
 FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS.
  
 50.1.2 THIS CHAPTER SHALL APPLY TO RESIDENTIAL COOKING
 EQUIPMENT
 USED FOR COMMERCIAL COOKING OPERATIONS. [96:1.1.2]
  
 50.2 GENERAL REQUIREMENTS.
 50.2.1 GENERAL.
 50.2.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING
 SMOKE
 OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN
 EXHAUST SYSTEM
 THAT COMPLIES WITH ALL THE EQUIPMENT AND PERFORMANCE
 REQUIREMENTS OF THIS CHAPTER. [96:4.1.1]
  
 9.2.3 COMMERCIAL COOKING OPERATIONS. WHERE REQUIRED BY
 ANOTHER
 SECTION OF THIS CODE, COMMERCIAL COOKING OPERATIONS
 SHALL BE PROTECTED
 IN ACCORDANCE WITH NFPA 96, STANDARD FOR VENTILATION
 CONTROL AND
 FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS,
 UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE
 PERMITTED TO BE CONTINUED IN SERVICE.
  
 PLEASE REVIEW AND CORRECT AND PROVIDE AN APPLICABLE
 NOTE OF ACKNOWLEDGEMENT.
  
  
  
 9) SHEET A 2.01 - THERE ARE ELEVATORS INDICATED.
  
 PER NFPA 101 CH 28 -
  
 28.5.3 ELEVATORS, ESCALATORS, AND CONVEYORS.
 28.5.3.1 ELEVATORS, ESCALATORS, AND CONVEYORS SHALL
 COMPLY WITH
 THE PROVISIONS OF SECTION 9.4.
 28.5.3.2* IN HIGH-RISE BUILDINGS, ONE ELEVATOR SHALL BE
 PROVIDED
 WITH A PROTECTED POWER SUPPLY AND SHALL BE AVAILABLE
 FOR USE BY
 THE FIRE DEPARTMENT IN CASE OF EMERGENCY.
  
  
 WHICH OF THE ELEVATORS MEET THE REQUIREMENTS?
  
  
  
  
 10) SHEET 2.01 - THERE ARE ELEVATORS INDICATED.
  
 PER THE STATE OF FLORIDA CHAPTER 399 FLORIDA STATUTES.
 SECTION 399.15, SECTION 17:
 REGIONAL EMERGENCY ELEVATOR ACCESS ?
 (1) IN ORDER TO PROVIDE EMERGENCY ACCESS TO ELEVATORS:
 (A) FOR EACH BUILDING IN THIS STATE WHICH IS SIX OR
 MORE STORIES IN HEIGHT, INCLUDING, BUT NOT LIMITED TO,
 HOTELS AND CONDOMINIUMS,
 ON WHICH A BUILDING PERMIT IS ISSUED AFTER SEPTEMBER
 30, 2006, ALL OF THE KEYS FOR ELEVATORS THAT ALLOW
 PUBLIC ACCESS, INCLUDING,
 BUT NOT LIMITED TO, SERVICE AND FREIGHT ELEVATORS, MUST
 BE KEYED SO AS TO ALLOW ALL ELEVATORS WITHIN EACH OF
 THE SEVEN STATE
 EMERGENCY RESPONSE REGIONS TO OPERATE IN FIRE EMERGENCY
 SITUATIONS WITH ONE MASTER ELEVATOR KEY.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE OF ACKNOWLEDGEMENT
  
  
  
  
  
 11) SHEET FP 1.00 - THERE ARE INDICATIONS OF SIDEWALL
 SPRINKLER HEADS AT THE BOTTOM OF HOISTWAYS.
  
 PER NFPA 13
  
 8.15.5 ELEVATOR HOISTWAYS AND MACHINE ROOMS.
  
 8.15.5.2 THE SPRINKLER REQUIRED AT THE BOTTOM OF THE
 ELEVATOR
 HOISTWAY BY 8.15.5.1 SHALL NOT BE REQUIRED FOR
 ENCLOSED, NONCOMBUSTIBLE
 ELEVATOR SHAFTS THAT DO NOT CONTAIN COMBUSTIBLE
 HYDRAULIC FLUIDS.
  
 PLEASE REVIEW AND CORRECT AND IF APPLICABLE THE
 SPRINKLER HEAD MAY BE REMOVED.
  
  
  
 12) SHEET FP 1.00 - THERE DOES NOT APPEAR TO BE A
 SPRINKLER HEAD IN THE SERVICE SINK ROOM.
  
 PER NFPA 101 TOTAL FIRE SPRINKLER COVERAGE IS REQUIRED.
  
 28.3.5 EXTINGUISHMENT REQUIREMENTS.
 28.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE
 WITH 28.3.5.3.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 13) SHEET FP 2.00 - THERE DOES NOT APPEAR TO BE A
 SPRINKLER HEAD IN THE SERVICE SINK ROOM.
  
 PER NFPA 101 TOTAL FIRE SPRINKLER COVERAGE IS REQUIRED.
  
 28.3.5 EXTINGUISHMENT REQUIREMENTS.
 28.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE
 WITH 28.3.5.3.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 14) SHEET FP 3.00 - THERE DOES NOT APPEAR TO BE A
 SPRINKLER HEAD IN THE SERVICE SINK ROOM.
  
 PER NFPA 101 TOTAL FIRE SPRINKLER COVERAGE IS REQUIRED.
  
 28.3.5 EXTINGUISHMENT REQUIREMENTS.
 28.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE
 WITH 28.3.5.3.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 15) SHEET FP 4.00 - THERE IS A SPRINKLER HEAD NEAR ST 2
 IN THE CORRIDOR AT THE CORRIDOR DOOR THAT APPEARS TO BE
 WITHIN THE WALL.
  
 ADDITIONALLY, THIS SHEET MAY BE INCORRECTLY LABLED AND
 NEED CORRECTION, SE BELOW.
  
 PLEASE REVIEW AND CORRECT THE LOCATION.
  
  
  
  
 16) SHEET FP 5.00 - THIS SHEET IS INDICATED AS 4TH THRU
 6TH FLOORS; HOWEVER, IT SHOWS THE ROOF.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 17) SHEET FP 4.00 - THERE IS AN INDICATION OF A
 SPRINKLER HEAD AT THE TOP OF THE ELEVATOR HOISTWAYS.
  
 PER NFPA 13
  
 8.15.5.5* UPRIGHT, PENDENT, OR SIDEWALL SPRAY
 SPRINKLERS SHALL
 BE INSTALLED AT THE TOP OF ELEVATOR HOISTWAYS.
 8.15.5.6 THE SPRINKLER REQUIRED AT THE TOP OF THE
 ELEVATOR HOISTWAY
 BY 8.15.5.5 SHALL NOT BE REQUIRED WHERE THE HOISTWAY
 FOR PASSENGER
 ELEVATORS IS NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE AND
 THE CAR ENCLOSURE MATERIALS MEET THE REQUIREMENTS OF
 ASME
 A17.1, SAFETY CODE FOR ELEVATORS AND ESCALATORS.
  
 PLEASE REVIEW AND REMOVE IF APPLICABLE.
  
  
  
 18) SHEET FP 1.00 - THERE IS A INDICATION AT NOTE 1
 THAT A SPRINKLER HEAD AT BENEATH OF STAIRWAY.
  
 PER NFPA 13
  
 8.15.3.2.3.1 SPRINKLERS SHALL BE PERMITTED TO BE
 OMITTED FROM
 THE BOTTOM OF THE STAIRWELL WHEN THE SPACE UNDER THE
 STAIRS AT
 THE BOTTOM IS BLOCKED OFF SO THAT STORAGE CANNOT OCCUR.
  
 PLEASE REVIEW AND CORRECT IF APPLICABLE AND PROVIDE FOR
 BLOCKING AREA.
  
  
  
 19) SHEET FP 9.00 - THERE ARE INDICATIONS OF FIRE LINE
 UNDERGROUND.
  
 ALL FIRE LINE UNDERGROUND SHALL BE INSTALLED, TESTED
 AND INSPECTED UNDER SEPARATE SHOP DRAWINGS AND PERMIT.
  
 FIRE LINE UNDERGROUND SHALL BE INSTALLED, TESTED AND
 INSPECTED PER NFPA 24,
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
  
 20) THERE DOES NOT APPEAR TO BE ANY CLEAR INFORMATION
 INDICATED FOR SMOKE CONTROL.
  
 PLEASE PROVIDE A DETAILED RATIONAL ANALYSIS INCL;UDING
 SEQUENCE OF OPERATION REGARDING SMOKE CONTROL FOR THIS
 PROJECT.
  
  
  
  
 21) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 22) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  