2019-03-04 10:56:57 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| |
| 1) SHEET A 2.01 - THERE IS AN INDICATION OF AN EMEGENCY |
| GENERATOR. THE GENERATOR INSTALLATION SHALL BE UNDER |
| SEPARATE SHOP DRAWINGS AND PERMIT. |
| |
| THE GENRATOR INSTALL SHALL ALSO COMPLY WITH THE |
| REQUIRMENTS OF NFPA 110, TO INCLUDE TYPE |
| |
| PER NFPA 110 |
| |
| CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY |
| SYSTEMS (EPSSS) |
| 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF |
| ELECTRICAL |
| POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO |
| LOADS FOR |
| A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND |
| WITHIN A SPECIFIED |
| TIME FOLLOWING LOSS OR FAILURE OF THE NORMAL POWER |
| SUPPLY |
| AS SPECIFIED IN TABLE 4.1(B). |
| |
| 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN |
| HOURS, FOR |
| WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD |
| WITHOUT |
| BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).] |
| 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN |
| SECONDS, |
| THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE |
| TRANSFER |
| SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE |
| 4.1(B) |
| PROVIDES THE TYPES DEFINED BY THIS STANDARD. |
| 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF |
| EQUIPMENT |
| INSTALLATION, PERFORMANCE, AND MAINTENANCE. |
| 4.4.1* LEVEL 1 SYSTEMS SHALL BE INSTALLED WHERE FAILURE |
| OF THE |
| EQUIPMENT TO PERFORM COULD RESULT IN LOSS OF HUMAN LIFE |
| OR |
| SERIOUS INJURIES. |
| 4.4.2* LEVEL 2 SYSTEMS SHALL BE INSTALLED WHERE FAILURE |
| OF THE |
| EPSS TO PERFORM IS LESS CRITICAL TO HUMAN LIFE AND |
| SAFETY. |
| 4.4.3 ALL EQUIPMENT SHALL BE PERMANENTLY INSTALLED. |
| 4.4.4* LEVEL 1 AND LEVEL 2 SYSTEMS SHALL ENSURE THAT |
| ALL LOADS |
| SERVED BY THE EPSS ARE SUPPLIED WITH ALTERNATE POWER |
| THAT |
| MEETS ALL THE FOLLOWING CRITERIA: |
| (1) OF A QUALITY WITHIN THE OPERATING LIMITS OF THE |
| LOAD |
| (2) FOR A DURATION SPECIFIED FOR THE CLASS AS DEFINED |
| IN TABLE |
| 4.1(A) |
| (3) WITHIN THE TIME SPECIFIED FOR THE TYPE AS DEFINED |
| IN TABLE |
| 4.1(B) |
| |
| PLEASE PROVIDE THE CLASSIFICATION, TYPE AND LEVEL ON |
| THIS MASTER PLAN AND AN APPLICABLE NOTE FOR SHOP |
| DRAWINGS. |
| |
| |
| 1A) SHEET M1.0A - THERE ARE NO FIRE CODE REFERENCES FOR |
| REVIEW OR COMPLIANCE. THE INSTALLATION SHALL COMPLY |
| WITH NFPA 110, STANDARD FOR |
| EMERGENCY AND STANDBY POWER SYSTEMS, 2013 EDITION |
| |
| PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN |
| APPLICABLE NOTE ACKNOWLEDGMENT OF THE ABOVE CODE. |
| |
| |
| |
| |
| |
| 2) SHEET A 2.01 - THE VENTILATION/EXHAUST SYSTEMS ARE |
| INDCATED WITH OPENINGS THAT MAY IN CONFLICT WITH THE |
| REQUIREMENTS PER ABOVE. |
| |
| |
| 7.7 HEATING, COOLING, AND VENTILATING. |
| 7.7.1* WITH THE EPS RUNNING AT RATED LOAD, VENTILATION |
| AIRFLOW |
| SHALL BE PROVIDED TO LIMIT THE MAXIMUM AIR TEMPERATURE |
| IN THE |
| EPS ROOM OR THE ENCLOSURE HOUSING THE UNIT TO THE |
| MAXIMUM |
| AMBIENT AIR TEMPERATURE REQUIRED BY THE EPS |
| MANUFACTURER. |
| 7.7.1.1 CONSIDERATION SHALL BE GIVEN TO ALL THE HEAT |
| EMITTED TO |
| THE EPS EQUIPMENT ROOM BY THE ENERGY CONVERTER, |
| UNINSULATED |
| OR INSULATED EXHAUST PIPES, AND OTHER HEAT-PRODUCING |
| EQUIPMENT. |
| 7.7.2 AIR SHALL BE SUPPLIED TO THE EPS EQUIPMENT FOR |
| COMBUSTION. |
| 7.7.2.1* FOR EPS SUPPLYING LEVEL 1 EPSS, VENTILATION |
| AIR SHALL |
| BE SUPPLIED DIRECTLY FROM A SOURCE OUTSIDE THE BUILDING |
| BY AN |
| EXTERIOR WALL OPENING OR FROM A SOURCE OUTSIDE THE |
| BUILDING BY |
| A 2-HOUR FIRE-RATED AIR TRANSFER SYSTEM. |
| 7.7.2.2 FOR EPS SUPPLYING LEVEL 1 EPSS, DISCHARGE AIR |
| SHALL BE |
| DIRECTED OUTSIDE THE BUILDING BY AN EXTERIOR WALL |
| OPENING OR TO |
| AN EXTERIOR OPENING BY A 2-HOUR FIRE-RATED AIR TRANSFER |
| SYSTEM. |
| 7.7.2.3 FIRE DAMPERS, SHUTTERS, OR OTHER SELF-CLOSING |
| DEVICES SHALL |
| NOT BE PERMITTED IN VENTILATION OPENINGS OR DUCTWORK |
| FOR SUPPLY |
| OR RETURN/DISCHARGE AIR TO EPS EQUIPMENT FOR LEVEL 1 |
| EPSS. |
| 7.7.3 VENTILATION AIR SUPPLY SHALL BE FROM OUTDOORS OR |
| FROM A |
| SOURCE OUTSIDE THE BUILDING BY AN EXTERIOR WALL OPENING |
| OR |
| FROM A SOURCE OUTSIDE THE BUILDING BY A 2-HOUR |
| FIRE-RATED AIR |
| TRANSFER SYSTEM. |
| 7.7.4 VENTILATION AIR SHALL BE PROVIDED TO SUPPLY AND |
| DISCHARGE |
| COOLING AIR FOR RADIATOR COOLING OF THE EPS WHEN |
| RUNNING |
| AT RATED LOAD. |
| 7.7.4.1 VENTILATION AIR SUPPLY AND DISCHARGE FOR |
| RADIATORCOOLED |
| EPS SHALL HAVE A MAXIMUM STATIC RESTRICTION OF 125 PA |
| (0.5 IN. OF WATER COLUMN) IN THE DISCHARGE DUCT AT THE |
| RADIATOR |
| OUTLET. |
| 7.7.4.2 RADIATOR AIR DISCHARGE SHALL BE DUCTED OUTDOORS |
| OR TO |
| AN EXTERIOR OPENING BY A 2-HOUR RATED AIR TRANSFER |
| SYSTEM. |
| 7.7.5 MOTOR-OPERATED DAMPERS, WHEN USED, SHALL BE |
| SPRING |
| OPERATED TO OPEN AND MOTOR CLOSED. FIRE DAMPERS, |
| SHUTTERS, OR |
| OTHER SELF-CLOSING DEVICES SHALL NOT BE PERMITTED IN |
| VENTILATION |
| OPENINGS OR DUCTWORK FOR SUPPLY OR RETURN/DISCHARGE AIR |
| TO |
| EPS EQUIPMENT FOR LEVEL 1 EPSS. |
| |
| PLEASE REVIEW AND ENSURE COMPLIANCE AND OR CORRECT AS |
| APPLICABLE. |
| |
| |
| |
| 3) SHEET A 2.01 - THERE IS AN OVERHEAD DOOR INDICATED |
| IN A 2 HOUR FIRE WALL AT THE STORAGE GARBAGGE ROOM. |
| |
| THERE IS NO FIRE RATING INDICATED ON THE DOOR SCHEDULE. |
| |
| ADDITIONALLY, WILL THIS DOOR BE ON A FUSIBLE LINK? |
| |
| PLEASE REVIEW AND CORRECT AND PROVIDE DETAILS. |
| |
| |
| |
| |
| 4) SHEET A 2.01 - THE EXITING FROM THE GENERATOR ROOM |
| INDICATES PASSAGE ALONG A 2 HOUR WALL; HOWEVER, THERE |
| IS A LOUVER INDICATED AT THAT WALL AREA. |
| |
| THE PATH OF TRAVEL IS REQUIRED TO BE PROTECTED PER NFPA |
| 101, CHAPTER 8 FEATURES OF FIRE PROTECTION |
| |
| 8.3.1.2* FIRE BARRIERS SHALL COMPLY WITH ONE OF THE |
| FOLLOWING: |
| (1) THE FIRE BARRIERS ARE CONTINUOUS FROM OUTSIDE WALL |
| TO OUTSIDE WALL |
| OR FROM ONE FIRE BARRIER TO ANOTHER, OR A COMBINATION |
| THEREOF, |
| INCLUDING CONTINUITY THROUGH ALL CONCEALED SPACES, SUCH |
| AS THOSE |
| FOUND ABOVE A CEILING, INCLUDING INTERSTITIAL SPACES. |
| (2) THE FIRE BARRIERS ARE CONTINUOUS FROM OUTSIDE WALL |
| TO OUTSIDE WALL |
| OR FROM ONE FIRE BARRIER TO ANOTHER, AND FROM THE FLOOR |
| TO THE |
| BOTTOM OF THE INTERSTITIAL SPACE, PROVIDED THAT THE |
| CONSTRUCTION |
| ASSEMBLY FORMING THE BOTTOM OF THE INTERSTITIAL SPACE |
| HAS A FIRE |
| RESISTANCE RATING NOT LESS THAN THAT OF THE FIRE |
| BARRIER. |
| 8.3.1.3 WALLS USED AS FIRE BARRIERS SHALL COMPLY WITH |
| CHAPTER 7 OF |
| NFPA 221, STANDARD FOR HIGH CHALLENGE FIRE WALLS, FIRE |
| WALLS, AND |
| FIRE BARRIER WALLS. THE NFPA 221 LIMITATION ON |
| PERCENTAGE WIDTH OF |
| OPENINGS SHALL NOT APPLY. |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| REFERENCES AND NARRATIVE. |
| |
| |
| |
| 5) SHEET A 2.01 - THERE IS AN INDICATION OF A EXIT FROM |
| THE GARAGE AREA PASSING BY A BOILER ROOM. |
| |
| 28.3.2 PROTECTION FROM HAZARDS. |
| 28.3.2.1 GENERAL. ALL ROOMS CONTAINING HIGH-PRESSURE |
| BOILERS, |
| REFRIGERATING MACHINERY, TRANSFORMERS, OR OTHER SERVICE |
| EQUIPMENT |
| SUBJECT TO POSSIBLE EXPLOSION SHALL NOT BE LOCATED |
| DIRECTLY UNDER OR |
| DIRECTLY ADJACENT TO EXITS AND SHALL BE EFFECTIVELY CUT |
| OFF FROM |
| OTHER PARTS OF THE BUILDING AS SPECIFIED IN SECTION |
| 8.7. |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| REFERENCES AND NARRATIVE |
| |
| |
| |
| 6) SHEET A 9.0 - THERE IS AN INDICATION OF A FP&L VAULT |
| BOX DIRECTLY BESIDE AN EXIT FROM STAIRWAY, ST 1. |
| |
| 28.3.2 PROTECTION FROM HAZARDS. |
| 28.3.2.1 GENERAL. ALL ROOMS CONTAINING HIGH-PRESSURE |
| BOILERS, |
| REFRIGERATING MACHINERY, TRANSFORMERS, OR OTHER SERVICE |
| EQUIPMENT |
| SUBJECT TO POSSIBLE EXPLOSION SHALL NOT BE LOCATED |
| DIRECTLY UNDER OR |
| DIRECTLY ADJACENT TO EXITS AND SHALL BE EFFECTIVELY CUT |
| OFF FROM |
| OTHER PARTS OF THE BUILDING AS SPECIFIED IN SECTION |
| 8.7. |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| REFERENCES AND NARRATIVE |
| |
| |
| |
| |
| 7) SHEET A 9.0 - THERE ARE DOORS THAT APPEAR TO OPEN |
| AND ENCROACH MORE THAN ONE HALF THE REQUIRED EGRESS |
| WIDTH; LUGGAGE ROOM, CONFERENCE SITTING AREA CORRIDOR |
| (3), THE EXIT DOOR AT ST 4, |
| |
| PER NFPA 101, CH 7 MEANS OF EGRESS |
| |
| 7.2.1.4.3* DOOR LEAF ENCROACHMENT. |
| 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| OF EGRESS |
| SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED |
| WIDTH OF AN AISLE, |
| A CORRIDOR, A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, |
| UNLESS BOTH |
| OF THE FOLLOWING CONDITIONS ARE MET: |
| (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| EXISTING |
| BUILDING. |
| (2) THE DOOR OPENING MEETS THE REQUIREMENT OF |
| 7.2.1.4.3.2. |
| |
| |
| |
| |
| 8) SHEET A 2.01 & A 2.03 - THERE APPEARS TO BE STOVE |
| TOPS INDICATED WITH THE KITCHENETTE AND BREAK ROOM. |
| |
| ANY KITCHEN EQUIPMENT WITHIN THESE ROOMS SHALL BE |
| PROTECTED PER NFPA 101 & 96 WITH ALL APPLICABLE HOODS |
| AND SUPPRESSION SYSTEMS UNDER SEPARATE SHOP DRAWINGS. |
| |
| PER NFPA 1 CH 50 & 101 CH 9: |
| |
| 50.1.1 THE DESIGN, INSTALLATION, OPERATION, INSPECTION |
| AND MAINTENANCE OF ALL PUBLIC AND PRIVATE COMMERCIAL |
| COOKING |
| EQUIPMENT SHALL COMPLY WITH THIS CHAPTER AND NFPA 96, |
| STANDARD |
| FOR VENTILATION CONTROL AND FIRE PROTECTION OF |
| COMMERCIAL COOKING OPERATIONS. |
| |
| 50.1.2 THIS CHAPTER SHALL APPLY TO RESIDENTIAL COOKING |
| EQUIPMENT |
| USED FOR COMMERCIAL COOKING OPERATIONS. [96:1.1.2] |
| |
| 50.2 GENERAL REQUIREMENTS. |
| 50.2.1 GENERAL. |
| 50.2.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING |
| SMOKE |
| OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN |
| EXHAUST SYSTEM |
| THAT COMPLIES WITH ALL THE EQUIPMENT AND PERFORMANCE |
| REQUIREMENTS OF THIS CHAPTER. [96:4.1.1] |
| |
| 9.2.3 COMMERCIAL COOKING OPERATIONS. WHERE REQUIRED BY |
| ANOTHER |
| SECTION OF THIS CODE, COMMERCIAL COOKING OPERATIONS |
| SHALL BE PROTECTED |
| IN ACCORDANCE WITH NFPA 96, STANDARD FOR VENTILATION |
| CONTROL AND |
| FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS, |
| UNLESS SUCH |
| INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS, |
| WHICH SHALL BE |
| PERMITTED TO BE CONTINUED IN SERVICE. |
| |
| PLEASE REVIEW AND CORRECT AND PROVIDE AN APPLICABLE |
| NOTE OF ACKNOWLEDGEMENT. |
| |
| |
| |
| 9) SHEET A 2.01 - THERE ARE ELEVATORS INDICATED. |
| |
| PER NFPA 101 CH 28 - |
| |
| 28.5.3 ELEVATORS, ESCALATORS, AND CONVEYORS. |
| 28.5.3.1 ELEVATORS, ESCALATORS, AND CONVEYORS SHALL |
| COMPLY WITH |
| THE PROVISIONS OF SECTION 9.4. |
| 28.5.3.2* IN HIGH-RISE BUILDINGS, ONE ELEVATOR SHALL BE |
| PROVIDED |
| WITH A PROTECTED POWER SUPPLY AND SHALL BE AVAILABLE |
| FOR USE BY |
| THE FIRE DEPARTMENT IN CASE OF EMERGENCY. |
| |
| |
| WHICH OF THE ELEVATORS MEET THE REQUIREMENTS? |
| |
| |
| |
| |
| 10) SHEET 2.01 - THERE ARE ELEVATORS INDICATED. |
| |
| PER THE STATE OF FLORIDA CHAPTER 399 FLORIDA STATUTES. |
| SECTION 399.15, SECTION 17: |
| REGIONAL EMERGENCY ELEVATOR ACCESS ? |
| (1) IN ORDER TO PROVIDE EMERGENCY ACCESS TO ELEVATORS: |
| (A) FOR EACH BUILDING IN THIS STATE WHICH IS SIX OR |
| MORE STORIES IN HEIGHT, INCLUDING, BUT NOT LIMITED TO, |
| HOTELS AND CONDOMINIUMS, |
| ON WHICH A BUILDING PERMIT IS ISSUED AFTER SEPTEMBER |
| 30, 2006, ALL OF THE KEYS FOR ELEVATORS THAT ALLOW |
| PUBLIC ACCESS, INCLUDING, |
| BUT NOT LIMITED TO, SERVICE AND FREIGHT ELEVATORS, MUST |
| BE KEYED SO AS TO ALLOW ALL ELEVATORS WITHIN EACH OF |
| THE SEVEN STATE |
| EMERGENCY RESPONSE REGIONS TO OPERATE IN FIRE EMERGENCY |
| SITUATIONS WITH ONE MASTER ELEVATOR KEY. |
| |
| PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN |
| APPLICABLE NOTE OF ACKNOWLEDGEMENT |
| |
| |
| |
| |
| |
| 11) SHEET FP 1.00 - THERE ARE INDICATIONS OF SIDEWALL |
| SPRINKLER HEADS AT THE BOTTOM OF HOISTWAYS. |
| |
| PER NFPA 13 |
| |
| 8.15.5 ELEVATOR HOISTWAYS AND MACHINE ROOMS. |
| |
| 8.15.5.2 THE SPRINKLER REQUIRED AT THE BOTTOM OF THE |
| ELEVATOR |
| HOISTWAY BY 8.15.5.1 SHALL NOT BE REQUIRED FOR |
| ENCLOSED, NONCOMBUSTIBLE |
| ELEVATOR SHAFTS THAT DO NOT CONTAIN COMBUSTIBLE |
| HYDRAULIC FLUIDS. |
| |
| PLEASE REVIEW AND CORRECT AND IF APPLICABLE THE |
| SPRINKLER HEAD MAY BE REMOVED. |
| |
| |
| |
| 12) SHEET FP 1.00 - THERE DOES NOT APPEAR TO BE A |
| SPRINKLER HEAD IN THE SERVICE SINK ROOM. |
| |
| PER NFPA 101 TOTAL FIRE SPRINKLER COVERAGE IS REQUIRED. |
| |
| 28.3.5 EXTINGUISHMENT REQUIREMENTS. |
| 28.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| AN |
| APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE |
| WITH 28.3.5.3. |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| |
| |
| 13) SHEET FP 2.00 - THERE DOES NOT APPEAR TO BE A |
| SPRINKLER HEAD IN THE SERVICE SINK ROOM. |
| |
| PER NFPA 101 TOTAL FIRE SPRINKLER COVERAGE IS REQUIRED. |
| |
| 28.3.5 EXTINGUISHMENT REQUIREMENTS. |
| 28.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| AN |
| APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE |
| WITH 28.3.5.3. |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| |
| |
| 14) SHEET FP 3.00 - THERE DOES NOT APPEAR TO BE A |
| SPRINKLER HEAD IN THE SERVICE SINK ROOM. |
| |
| PER NFPA 101 TOTAL FIRE SPRINKLER COVERAGE IS REQUIRED. |
| |
| 28.3.5 EXTINGUISHMENT REQUIREMENTS. |
| 28.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| AN |
| APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE |
| WITH 28.3.5.3. |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| |
| 15) SHEET FP 4.00 - THERE IS A SPRINKLER HEAD NEAR ST 2 |
| IN THE CORRIDOR AT THE CORRIDOR DOOR THAT APPEARS TO BE |
| WITHIN THE WALL. |
| |
| ADDITIONALLY, THIS SHEET MAY BE INCORRECTLY LABLED AND |
| NEED CORRECTION, SE BELOW. |
| |
| PLEASE REVIEW AND CORRECT THE LOCATION. |
| |
| |
| |
| |
| 16) SHEET FP 5.00 - THIS SHEET IS INDICATED AS 4TH THRU |
| 6TH FLOORS; HOWEVER, IT SHOWS THE ROOF. |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| |
| |
| 17) SHEET FP 4.00 - THERE IS AN INDICATION OF A |
| SPRINKLER HEAD AT THE TOP OF THE ELEVATOR HOISTWAYS. |
| |
| PER NFPA 13 |
| |
| 8.15.5.5* UPRIGHT, PENDENT, OR SIDEWALL SPRAY |
| SPRINKLERS SHALL |
| BE INSTALLED AT THE TOP OF ELEVATOR HOISTWAYS. |
| 8.15.5.6 THE SPRINKLER REQUIRED AT THE TOP OF THE |
| ELEVATOR HOISTWAY |
| BY 8.15.5.5 SHALL NOT BE REQUIRED WHERE THE HOISTWAY |
| FOR PASSENGER |
| ELEVATORS IS NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE AND |
| THE CAR ENCLOSURE MATERIALS MEET THE REQUIREMENTS OF |
| ASME |
| A17.1, SAFETY CODE FOR ELEVATORS AND ESCALATORS. |
| |
| PLEASE REVIEW AND REMOVE IF APPLICABLE. |
| |
| |
| |
| 18) SHEET FP 1.00 - THERE IS A INDICATION AT NOTE 1 |
| THAT A SPRINKLER HEAD AT BENEATH OF STAIRWAY. |
| |
| PER NFPA 13 |
| |
| 8.15.3.2.3.1 SPRINKLERS SHALL BE PERMITTED TO BE |
| OMITTED FROM |
| THE BOTTOM OF THE STAIRWELL WHEN THE SPACE UNDER THE |
| STAIRS AT |
| THE BOTTOM IS BLOCKED OFF SO THAT STORAGE CANNOT OCCUR. |
| |
| PLEASE REVIEW AND CORRECT IF APPLICABLE AND PROVIDE FOR |
| BLOCKING AREA. |
| |
| |
| |
| 19) SHEET FP 9.00 - THERE ARE INDICATIONS OF FIRE LINE |
| UNDERGROUND. |
| |
| ALL FIRE LINE UNDERGROUND SHALL BE INSTALLED, TESTED |
| AND INSPECTED UNDER SEPARATE SHOP DRAWINGS AND PERMIT. |
| |
| FIRE LINE UNDERGROUND SHALL BE INSTALLED, TESTED AND |
| INSPECTED PER NFPA 24, |
| |
| PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| ACKNOWLEDGEMENT. |
| |
| |
| |
| |
| 20) THERE DOES NOT APPEAR TO BE ANY CLEAR INFORMATION |
| INDICATED FOR SMOKE CONTROL. |
| |
| PLEASE PROVIDE A DETAILED RATIONAL ANALYSIS INCL;UDING |
| SEQUENCE OF OPERATION REGARDING SMOKE CONTROL FOR THIS |
| PROJECT. |
| |
| |
| |
| |
| 21) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| |
| 22) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |