2019-04-03 18:50:36PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 FOR INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR AT
 822-1515 OR E-MAIL: [email protected]
  
 2) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING AND
 IS REQUIRED TO COMPLY WITH THE FOLLOWING:
 THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE.
  
 G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL
 BE HAPPY TO SEND YOU A COPY OF THE OCTOBER 2018
 GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS.
  
 3) 109.3 BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL EFFECTIVELY BE THE VALUE OF THE
 BUILDING THAT THE PERMIT FEES WILL BE BASED ON FOR THIS
 PERMIT. THE BUILDING DEPARTMENT DOES NOT WANT TO
 COLLECT TWICE FOR THE VALUE OF THESE SUB-PERMITS NOT
 COVERED UNDER THE PRIME OR MASTER PERMIT.
  
 4) PROVIDE A PER FLOOR AREA BREAKDOWN FOR EACH
 OCCUPANCY TYPE ON THAT FLOOR. THIS IS REQUIRED IN ORDER
 TO DO AN ACCURATE VALUATION AMOUNT FOR THE BUILDING.
 FBC 109.3
  
 5) THE STRUCTURAL DRAWINGS HAVE NOT BEEN SIGNED AND
 SEALED BY THE DESIGN PROFESSIONAL OF RECORD AS REQUIRED
 BY FS 471 OR FS 481 AND ARE MARKED "NOT FOR
 CONSTRUCTION".
  
 6) THE CODE ANALYSIS ON SHEET A-1.00A, SPECIFIES THE
 HOTEL AND EXTENDED STAY ROOMS AS OCCUPANCY GROUP AS
 R-1. THE EXTENDED STAY ROOMS PROVIDE COMPLETE
 INDEPENDENT LIVING FACILITIES INCLUDING PERMANENT
 PROVISIONS FOR COOKING AND MEET THE DEFINITION OF A
 DWELLING UNIT IN CHAPTER 2 OF THE BUILDING CODE. WILL
 THE EXTENDED STAY ROOMS BE RENTED OR LEASED TO THE SAME
 OCCUPANT FOR MORE THAN 30 DAYS? IF SO, THEY ARE
 CLASSIFIED AS HOTEL (NON-TRANSIENT) AND GROUP R-2. THIS
 WILL REQUIRE THESE ROOMS TO TO COMPLY WITH FAIR HOUSING
 GUIDELINES. FBC SECTION 310
  
 7) SUBMIT THE APPROPRIATE FORMS TO SHOW COMPLIANCE WITH
 THE SECTION C401.2 OF THE 2014 FBC ENERGY CONSERVATION.
  
 8) SUBMIT A GEOTECHNICAL (SOIL INVESTIGATION) REPORT
 FOR THE PROJECT. FBC 1803
  
 9) FBC ACCESSIBILITY SECTION 208.2.4 REQUIRES ONE VAN
 PARKING SPACE FOR EVERY SIX OR FRACTION OF SIX
 ACCESSIBLE PARKING SPACES. SPECIFY THE LOCATION OF THE
 DESIGNATED VAN PARKING SPACES ON THE PLANS.
  
 10) THE OVERALL FLOOR PLANS LEGEND AND NOTES ON SHEET
 A-2.00 SPECIFIES THAT A SHADED AREA WILL BE INDICATED
 WHERE THE 8'-3" CLEAR AREA FOR VAN PARKING AND DRIVEWAY
 WILL BE PROVIDED. I DID NOT SEE THIS ON THE PLANS.
 PLEASE CLARIFY. FBC 107.2.1
  
 11) ON SHEET A-2.00, THE LEGEND FOR THE ONE AND TWO
 HOUR RATED WALLS IS NOT FOLLOWED ON THE PLANS. TWO
 SHORT DASHES BETWEEN THE LONG DASHES IS USED FOR THE 1
 HOUR FIRE RATED WALLS AND A LINE OF DASHES IS USED FOR
 THE 2 HOUR FIRE RATED WALLS. PLEASE REVISE. FBC 107.2.1
  
 12) THE SWIMMING POOL IS REQUIRED TO HAVE A SEPARATE
 PERMIT. ACCESS TO THE POOL AREA FROM THE BUILDING AND
 THE PRIVATE COURTYARDS ARE REQUIRED TO COMPLY WITH THE
 POOL BARRIER REQUIREMENTS OF FBC 454.2.17.
  
 13) ACCESS INTO AND OUT OF THE SWIMMING POOL IS
 REQUIRED TO BE ACCESSIBLE. FBC ACCESSIBILITY 242.2 AT
 LEAST TWO ACCESSIBILE MEANS OF ENTRY SHALL BE PROVIDED
 FOR SWIMMING POOLS. SHOW HOW THE POOL WILL COMPLY.
  
 14) THE FBC ACCESSIBILITY TABLE 224.2 REQUIRES 10 GUEST
 ROOMS WITH MOBILITY FEATURES. THREE OF THE ROOMS ARE
 REQUIRED TO HAVE ROLL-IN SHOWERS. SECTION 224.6.3
 REQUIRES A NUMBER OF ROOMS EQUALING 5% OF THE GUEST
 ROOMS MINUS THE TOTAL ACCESSIBLE ROOMS REQUIRED BY
 TABLE 224.2 TO PROVIDE SPECIAL ACCESSIBILITY FEATURES
 OF 806.4. TAKING 5 PERCENT OF 224 IS 11.2 OR 12.
 SUBTRACTING 10 FROM 12 LEAVES 2. THEREFORE IN ADDITION
 TO THE TEN (10) ADA QUEST ROOMS WITH MOBILITY FEATURES
 AN ADDITIONAL TWO (2) ROOMS WOULD BE REQUIRED TO COMPLY
 WITH 806.4. THE NUMBER OF ADA MOBILITY ROOMS SPECIFIED
 ON SHEET A-1.00A IS 14. THIS WILL MEET OR EXCEED THE
 NUMBER OF ROOMS REQUIRED.
  
 15) THE FBC ACCESSIBILITY TABLE 224.4 REQUIRES 17 GUEST
 ROOMS WITH COMMUNICATION FEATURES. SECTION 224.5
 DISPERSION REQUIRES AT LEAST ONE GUEST ROOM REQUIRED TO
 PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL
 ALSO PROVIDE COMMUNICATION FEATURES COMPLYING WITH
 806.3. NOT MORE THAN 10 PERCENT OF GUEST ROOMS REQUIRED
 TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL
 BE USED TO SATISFY THE MINIMUM NUMBER OF GUEST ROOMS
 REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING
 WITH 806.3. TEN PERCENT OF THE 10 REQUIRED GUEST ROOMS
 WITH MOBILITY FEATURES IS ONE (1). THEREFORE, ONLY ONE
 OF THE REQUIRED 17 GUEST ROOMS WITH COMMUNICATION
 FEATURES CAN BE A GUEST ROOM WITH MOBILITY FEATURES.
 PLEASE REVISE PLANS TO COMPLY.
  
 16) FBC ACCESSIBILITY SECTION 209.4 REQUIRES PARKING
 FACILITIES THAT PROVIDE VALET PARKING SERVICES TO
 PROVIDE AT LEAST ONE PASSENGER LOADING ZONE COMPLYING
 WITH SECTION 503. SHOW THAT THE PASSENGER DROP OF AREA
 ON THE PLANS COMPLIES WITH SECTION 503 OF THE FLORIDA
 ACCESSIBILITY CODE.
  
 17) SPECIFY THE LIVE LOADS REQUIRED BY FBC TABLE 1607.1
 FOR EACH AREA OF THE BUILDING ON THE PLANS.
  
 18) THE PLANS SPECIFY THAT THE PARKING GARAGE IN THIS
 BUILDING IS AN OPEN GARAGE. THIS DOES NOT APPEAR TO BE
 AN OPEN GARAGE. THE OPENINGS DO NOT MEET THE
 REQUIREMENT OF FBC 406.5.2 FOR BEING UNIFORMLY
 DISTRIBUTED ON AT LEAST TWO SIDES OF THE STRUCTURE. THE
 CALCULATIONS FOR THE AREA OF OPENINGS IN THE EXTERIOR
 WALLS APPEARS TO BE INCORRECT. FBC 406.5 REQUIRES THE
 AREA OF SUCH OPENINGS IN EXTERIOR WALLS ON A TIER TO BE
 NOT LESS THAN 20 PERCENT OF THE TOTAL PERIMETER WALL
 AREA OF EACH TIER. REVISE PLANS FOR AN ENCLOSED GARAGE.
  
 19) THERE IS A PROBLEM WITH THE CALCULATIONS FOR THE 25
 PERCENT ALLOWABLE AREA OF EXTERIOR WALL OPENINGS FOR
 THE WEST BUILDING ELEVATION. FBC 705.8.1 STATES THAT
 THE MAXIMUM AREA OF UNPROTECTED AND PROTECTED OPENINGS
 IN AN EXTERIOR WALL IN ANY STORY SHALL NOT EXCEED THE
 PERCENTAGES SPECIFIED IN TABLE 705.8. THE TABLE ALLOWS
 25 PERCENT OPENINGS FOR A FIRE SEPARATION DISTANCE OF 5
 FEET TO LESS THAN 10 FEET. THE OPENING AREA IN THE WALL
 OF THE PARKING GARAGE EXCEEDS THE ALLOWABLE OPENING
 AREA ON THE GROUND STORY AND THE MEZZANINE STORY.THE
 OPENINGS IN THE WALLS OF EACH STORY OF THE TOWERS ON
 EACH SIDE OF THE POOL DECK MEET THE 25 PERCENT
 REQUIREMENT.
  
 20) THE LIFE SAFETY PLANS NEED TO SHOW THE FOLLOWING
 FOR EACH FLOOR:
 A) THE NUMBER OF OCCUPANTS IN EACH AREA FBC 1004.1
 B) THE CUMULATIVE OCCUPANT LOADS FBC 1004.1.1
 C) THE EXIT SEPARATION DISTANCE FBC 1015.2.1
 D) THE COMMON PATH OF EGRESS TRAVEL DISTANCE FBC 1014.3
 E) THE EXIT ACCESS TRAVEL DISTANCE FBC 1016.3
 F) THE CLEAR WIDTH OF THE EXIT OR EXIT ACCESS DOORS FBC
 1008.1.1
 G) THE CAPACITY OF EGRESS DOORS, OCCUPANT LOAD SERVED
 AND MEANS OF EGRESS FACTOR FBC1005.3.2
 H) THE DISTRIBUTION OF EGRESS CAPACITY FBC1005.5
  
 21) THE WINDOW SCHEDULE ON SHEET A-8.01 LISTS TWO
 DIFFERENT WINDOWS FOR MARK "D". CLARIFY. FBC 107.2.1
  
 22) THE LINEN CHUTE SECTION ON SHEET A-6.02 HAS THE
 TERMINATION ROOM AND THE ACCESS ROOMS LABELED AS
 GARBAGE ROOMS. PLEASE CORRECT. FBC 713.13.1
  
 23) ITEM #26 ON SHEET A-6.00 SPECIFIES 1 X 4 P.T. WOOD
 IN 2 HOUR FIRE RATED SHAFTS, WHICH ARE SHOWN IN THE
 SHAFT WALL SECTIONS ON SHEET A-6.02. WOOD IS NOT
 ALLOWED IN FIRE RATED SHAFT WALLS UNLESS IT IS PART OF
 THE LISTED ASSEMBLY. CORRECT. FBC 713.2
  
 24) PROVIDE ROOF DRAINAGE, ROOF DRAIN SIZING AND
 OVER-FLOW SCUPPER CALCULATIONS. FBC 1503.4
  
 25) THE PROJECT IS NOT LOCATED IN A SPECIAL FLOOD
 HAZARD AREA. THE ELEVATIONS ON THE DRAWINGS ARE GIVEN
 IN NGVD 29 DATUM. THE CITY OF WEST PALM BEACH ADOPTED
 NEW FLOOD MAPS ON OCTOBER 5, 2017. THESE NEW MAPS USE
 NAVD 88 AS THE VERTICAL DATUM. IN ORDER TO AVOID ANY
 CONFUSION WITH ELEVATIONS IT WOULD BE GOOD TO REPLACE
 THE ELEVATIONS ON THE PLANS WITH THE CURRENT VERTICLE
 DATUM, NAVD 88 OR TO PROVIDE BOTH THE NAVD AND THE NGVD
 ELEVATIONS ON THE PLANS. FBC 107.2.1
  
 26) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  
  