Date |
Text |
2018-01-08 12:21:32 | FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED |
| NFPA 70 2011 EDITION |
| |
| JAKE LEAHY |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| |
| |
| C405.2.5 EXTERIOR LIGHTING CONTROLS. |
| |
| LIGHTING FOR EXTERIOR APPLICATIONS OTHER THAN EMERGENCY |
| LIGHTING THAT IS INTENDED TO BE AUTOMATICALLY OFF |
| DURING BUILDING OPERATION, LIGHTING SPECIFICALLY |
| REQUIRED TO MEET HEALTH AND LIFE SAFETY REQUIREMENTS OR |
| DECORATIVE GAS LIGHTING SYSTEMS SHALL: |
| |
| 1.BE PROVIDED WITH A CONTROL THAT AUTOMATICALLY TURNS |
| OFF THE LIGHTING AS A FUNCTION OF AVAILABLE DAYLIGHT. |
| |
| 2.WHERE LIGHTING THE BUILDING FA?ADE OR LANDSCAPE, THE |
| LIGHTING SHALL HAVE CONTROLS THAT AUTOMATICALLY SHUT |
| OFF THE LIGHTING AS A FUNCTION OF DAWN/DUSK AND A SET |
| OPENING AND CLOSING TIME. |
| |
| 3.WHERE NOT COVERED IN ITEM 2, THE LIGHTING SHALL HAVE |
| CONTROLS CONFIGURED TO AUTOMATICALLY REDUCE THE |
| CONNECTED LIGHTING POWER BY NOT LESS THAN 30 PERCENT |
| FROM NOT LATER THAN MIDNIGHT TO 6 A.M., FROM ONE HOUR |
| AFTER BUSINESS CLOSING TO ONE HOUR BEFORE BUSINESS |
| OPENING OR DURING ANY PERIOD WHEN ACTIVITY HAS NOT BEEN |
| DETECTED FOR A TIME OF LONGER THAN 15 MINUTES. |
| |
| ALL TIME SWITCHES SHALL BE ABLE TO RETAIN PROGRAMMING |
| AND THE TIME SETTING DURING LOSS OF POWER FOR A PERIOD |
| OF AT LEAST 10 HOURS. |
| |
| EXCEPTION: LIGHTING FOR COVERED VEHICLE ENTRANCES OR |
| EXITS FROM BUILDINGS OR PARKING STRUCTURES WHERE |
| REQUIRED FOR SAFETY, SECURITY OR EYE ADAPTATION. |
| |