| ****PLAN REVIEW COMMENTS**** |
| |
| ART LANGE BUILDING PLANS EXAMINER |
| |
| DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS STREET |
| WEST PALM BEACH, FL 33402 |
| 561-805-6718 [email protected] |
| |
| |
| NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW |
| COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| SECOND REVIEW: |
| |
| 5- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC. |
| R401.3 FBC-RESIDENTIAL. |
| |
| NOT ADDRESSED. NOTE: NEED DRAINAGE PLAN. SEE CITY |
| AMENDMENTS SEC. 107.2.5 BELOW. |
| |
| PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC. |
| R401.3 FBC-RESIDENTIAL. |
| |
| |
| SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN |
| SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE |
| SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE |
| FIRST 10 FEET (3048 MM). |
| EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE |
| BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 |
| PERCENT AWAY FROM THE BUILDING. |
| |
| |
| |
| ------------------------------------------------------- |
| ----------------------------- |
| |
| DEFERRED SUBMITTALS |
| |
| 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| |
| A) ENTRY DOOR WITH SIDELITES AND TRANSOM AS SHOWN ON |
| PLANS. |
| |
| B) SINGLE HUNG WINDOWS AS SPECIFIED ON PLANS. |
| |
| C) HORIZONTAL ROLLER WINDOWS AS SPECIFIED ON PLANS. |
| |
| D) SLIDING GLASS DOORS AS SHOWN ON PLANS. |
| |
| E) HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| HURRICANE IMPACT GLAZING. AND, PROVIDE COMPLETE |
| INSTALLATION SCHEDULE. SEE CITY SAMPLE. |
| |
| F) ROOF SHINGLES. |
| |
| G) ROOF SHINGLES UNDERLAYMENT AS SPECIFIED ON PLANS. |
| (COORDINATE WITH ITEM #9(B) ABOVE. |
| |
| H) RIDGE VENTS AS SPECIFIED ON PLANS. SEE SHEET A-1. |
| |
| I) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| |
| 13- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL |
| PRODUCT APPROVALS (NOT SIGNING AND SEALING) AS REQUIRED |
| BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| |