Plan Review Notes
Plan Review Notes For Permit 17120974
Permit Number 17120974
Review Stop P
Sequence Number 2
Notes
Date Text
2018-08-28 15:37:54PERMIT 17 120974
 PLUMBING REVIEW SEQUENCE 2
  
 COMMENTS FROM SEQUENCE 1
  
 1-SHEET P100 NOTE READS "GAS OUTER"
 RESPONSE: REFER TO SHEET P100 FOR SPELLING REVISION
 SEQUENCE 2 COMMENT(S): APPROVED
  
 2-SHEET P100 SHOWS WATER SERVICE RUNNING TO BACK OF
 PROPERTY WHERE THERE IS AN EXISTING HOME NOW; WILL THIS
 BE DEMOLISHED? PLEASE CLARIFY PER WPB AMEND TO FBC
 107.2.1
 RESPONSE: EXISTING HOME
 SEQUENCE 2 COMMENT(S): DENIED. PLEASE SEE REVIEW STOP
 B-BUILDING, 2ND REVIEW,NOTE 3. RESPONSE BY RPJ TO
 PLUMBING REVIEW FOR REVIEW 3 NOT REQUIRED
  
 3-SHEET P102 IS MISSING FROM FROM PLAN SET.PLEASE
 PROVIDE TWO FULL SETS OF PLANS PER WPB AMEND TO FBC
 107.2.1
 RESPONSE: REFER TO ATTACHED SHEET P102 (FURNISHED REV 1
 DATED 6-19-18)
 SEQUENCE 2 COMMENT(S): STORM PIPING FOR COURTYARD IS
 NOT SIZED AND SQUARE FOOTAGE IS NOT INDICATED; CORRECT
 AND RESUBMIT
  
 4-PLEASE LABEL THE BATHROOMS ON THE ISOMETRIC DRAWING
 PER WPB AMEND TO FBC 107.2.1
 RESPONSE: PLEASE REFER TO SHEET P201
 SEQUENCE 2 COMMENT(S): SANITARY ISOMETRIC IS LABELED,
 HOWEVER "POWDER" FOR THE POWDER ROOM IS MISPELLED
 "POWER"; CORRECT AND RESUBMIT
  
 5-PROVIDE STORM WATER ISOMETRIC PER WPB AMEND TO FBC
 107.3.5.3(11)
 RESPONSE: WPB AMENDMENT ONLY APPLIES TO FBC 2010, NOT
 2014. PERMIT DRAWINGS INCLUDE SANITARY, WATER AND GAS
 PIPING RISERS. STORM DRAINAGE SYSTEM INDICATED IN FLOOR
 PLANS IS PROPERLY SIZED WITH RESPECTIVE FLOOR AREAS
 INDICATED. FBC RESIDENTIAL DOES NOT REQUIRE PIPING
 RISERS.
 SEQUENCE 2 COMMENT(S): WPB DID NOT ADOPT 2014 BUT
 ADOPTED 2017 WHEN IT BECAME AVAILABLE, THEREFORE THE
 2010 APPLIES TO THE 2014 FBC; CORRECT AND RESUBMIT.
  
 6-SHEET P201; THE TOILET FOR BATHROOM #2 SHALL CONNECT
 TO THE BATHROOM GROUP WITH THE SHOWER AND LAVATORY PER
 FBC RES P3108.1
 RESPONCE: NOT NOTED ON RPJ LETTER, BUT SHEET P201 HAS
 BEEN CORRECTLY MODIFIED TO MEET THIS REQUIREMENT
 SEQUENCE 2 COMMENT(S): SHEET P201 MODIFICATION
 APPROVED. PLEASE REVISE PLAN VIEW ON SHEET P104 TO
 REFLECT THE CHANGE.
  
 7-THE VALVES FOR THE STACKABLE WASHING MACHINES SHALL
 BE ACCESSIBLE PER FBC RES P2803.9.3
 RESPONCE: NOT NOTED ON RPJ LETTER, BUT SHEET P201 HAS
 BEEN CORRECTLY MODIFIED TO MEET THIS REQUIREMENT
 SEQUENCE 2 COMMENT(S): SHEET P201 MODIFICATION
 APPROVED. PLEASE ADVISE IF THE APPURTENANCES SHOWN ON
 THE WATER SUPPLY OUTLETS ON THE WATER RISER DIAGRAM FOR
 THE WASHING MACHINES, ICE LINES AND DISH WASHERS ARE
 WATER HAMMER ARRESTORS AS REQUIRED BY RES FBC 2903.5.
 PLEASE ID THEM ON THE WATER RISER DIAGRAM.
  
 SEQUENCE 2 COMMENT(S): NEW ITEM
 1-RE: SHEET P103; GAZEBO STORM WATER PING FOR TRENCH
 DRAIN IS NOT SHOWN. FURNISH PIPING AND SIZING AND
 RESUBMIT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561-805-6711