2018-02-02 18:10:081ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SIZE THE BRANCH TO GENERATOR. PER WPB AMEND TO FBC
 107.2.1
  
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR INDOOR
 APPLIANCES PER THE FBC-2014 FUEL GAS CODE SEC. 304.
  
 3. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS AND
 INSTALLATION GUIDES FOR ALL GAS EQUIPMENT AND
 REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 4. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  