2018-01-19 08:35:26 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. THERE IS A DISCREPANCY WITH THE FIRE ALARM RISER AND |
| WHAT IS SHOWN ON PLANS FOR SMOKE/CO ALARMS. THE RISER |
| DIAGRAM ON SHEET E-202 STATES THIS INSTALLATION WILL |
| COMPLY WITH NEC 760, BUT ALSO SHOWS STANDARD 120 VOLT |
| SMOKE AND CO ALARMS, WHICH ARE NOT COVERED BY NEC 760. |
| TYPICAL SMOKE AND CO ALARMS ARE WIRED FROM A 120 VOLT |
| BRANCH CIRCUIT CONTROLLED WITH AN AFCI BREAKER. PROVIDE |
| CLARIFICATION AND/OR CORRECTION. FBC 107.2.1; FBC RE |
| R314.3, R315.1 |
| 2. SHEET E-202, LEGEND GENERAL NOTES, STATES THAT CODE |
| IS BASED ON NEC 2008, WHICH IS NOT THE CODE FOR THIS |
| PROJECT. ALSO, NOTE 2 SITES NEC 406.11 FOR TAMPER |
| RESISTANT RECEPTACLES, WHICH IS NOT THE CURRENT CODE |
| SECTION FOR THIS REQUIREMENT. PROVIDE CORRECTIONS. FBC |
| PREFACE, NEC 2011, SECTION 406.12 |
| 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, |
| 107.2.1 |
| 4. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE |
| ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND |
| CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF |
| GROUNDING ELECTRODE SYSTEM AND WIRING ADDED TO WHAT IS |
| SHOWN. NEC 250.32; FBC RE3607.3 |
| 5. BBQ TERRACE SHOWS RECEPTACLE OUTLETS THAT ARE NOT |
| GFCI PROTECTED. ALL RECEPTACLES OUTSIDE REQUIRE GFCI |
| PROTECTION. NEC 210.8(A) |
| 6. CIRCUIT A-29 IS SHOWN AS THE WASHING MACHINE AND AS |
| GFCI RECEPTACLES IN BATHROOMS. A MINIMUM OF ONE 20 |
| AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY |
| BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE |
| NO OTHER OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3) |
| 7. UPPER LAUNDRY ROOM (ROOM 211) SHOWS WHAT APPEARS TO |
| BE COUNTER SPACE IN FRONT OF THE ELECTRICAL PANELS. |
| PANELS ARE REQUIRED TO HAVE CLEARANCE PER NEC 110.26. |
| PROVIDE CLARIFICATION AND/OR CORRECTION. NEC 110.26 |
| 8. MORNING BAR (ROOM 222) SHOWS A RECEPTACLE ON CIRCUIT |
| 2E-4 WITHIN 6 FEET OF A SINK THAT IS NOT GFCI |
| PROTECTED. PROVIDE CORRECTION. NEC 210.8(A) |
| 9. GUEST BATH (ROOM 241) SHOWS A RECEPTACLE THAT IS NOT |
| GFCI PROTECTED. PROVIDE CORRECTION. NEC 210.8(A) |
| 10. THERE IS A SMALL SQUARE SYMBOL USED FOR LIGHT |
| FIXTURE THAT IS NOT EXPLAINED IN THE LEGEND THIS |
| FIXTURE IS SHOWN IN MANY CLOSET LOCATIONS. PER CODE: |
| "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND |
| PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE |
| PERMITTED IN CLOTHES CLOSETS". PROVIDE CLARIFICATION |
| AND/OR CORRECTION. NEC 410.16 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |