2018-01-19 08:35:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THERE IS A DISCREPANCY WITH THE FIRE ALARM RISER AND
 WHAT IS SHOWN ON PLANS FOR SMOKE/CO ALARMS. THE RISER
 DIAGRAM ON SHEET E-202 STATES THIS INSTALLATION WILL
 COMPLY WITH NEC 760, BUT ALSO SHOWS STANDARD 120 VOLT
 SMOKE AND CO ALARMS, WHICH ARE NOT COVERED BY NEC 760.
 TYPICAL SMOKE AND CO ALARMS ARE WIRED FROM A 120 VOLT
 BRANCH CIRCUIT CONTROLLED WITH AN AFCI BREAKER. PROVIDE
 CLARIFICATION AND/OR CORRECTION. FBC 107.2.1; FBC RE
 R314.3, R315.1
 2. SHEET E-202, LEGEND GENERAL NOTES, STATES THAT CODE
 IS BASED ON NEC 2008, WHICH IS NOT THE CODE FOR THIS
 PROJECT. ALSO, NOTE 2 SITES NEC 406.11 FOR TAMPER
 RESISTANT RECEPTACLES, WHICH IS NOT THE CURRENT CODE
 SECTION FOR THIS REQUIREMENT. PROVIDE CORRECTIONS. FBC
 PREFACE, NEC 2011, SECTION 406.12
 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 4. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF
 GROUNDING ELECTRODE SYSTEM AND WIRING ADDED TO WHAT IS
 SHOWN. NEC 250.32; FBC RE3607.3
 5. BBQ TERRACE SHOWS RECEPTACLE OUTLETS THAT ARE NOT
 GFCI PROTECTED. ALL RECEPTACLES OUTSIDE REQUIRE GFCI
 PROTECTION. NEC 210.8(A)
 6. CIRCUIT A-29 IS SHOWN AS THE WASHING MACHINE AND AS
 GFCI RECEPTACLES IN BATHROOMS. A MINIMUM OF ONE 20
 AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY
 BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE
 NO OTHER OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3)
 7. UPPER LAUNDRY ROOM (ROOM 211) SHOWS WHAT APPEARS TO
 BE COUNTER SPACE IN FRONT OF THE ELECTRICAL PANELS.
 PANELS ARE REQUIRED TO HAVE CLEARANCE PER NEC 110.26.
 PROVIDE CLARIFICATION AND/OR CORRECTION. NEC 110.26
 8. MORNING BAR (ROOM 222) SHOWS A RECEPTACLE ON CIRCUIT
 2E-4 WITHIN 6 FEET OF A SINK THAT IS NOT GFCI
 PROTECTED. PROVIDE CORRECTION. NEC 210.8(A)
 9. GUEST BATH (ROOM 241) SHOWS A RECEPTACLE THAT IS NOT
 GFCI PROTECTED. PROVIDE CORRECTION. NEC 210.8(A)
 10. THERE IS A SMALL SQUARE SYMBOL USED FOR LIGHT
 FIXTURE THAT IS NOT EXPLAINED IN THE LEGEND THIS
 FIXTURE IS SHOWN IN MANY CLOSET LOCATIONS. PER CODE:
 "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND
 PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS". PROVIDE CLARIFICATION
 AND/OR CORRECTION. NEC 410.16
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER