2018-04-17 18:34:5704/17/2018 2ND PLUMBING REVIEW**DENIED**
  
 1) ADDRESS MUST BE ON PLAN. FBC 107.2.1
  
 2) THE WATER HEATER ON YOUR FLORIDA ENERGY EFFICIENCY
 FORM R405-2014 IS SHOWING THE E.F AS .92. AS OF APRIL
 16, 2015 ALL RESIDENTIAL WATER HEATERS ARE REQUIRED TO
 BE A MIN .95 E.F UP TO 55 GALLONS. THIS IS DEFINED IN
 THE CODE OF FEDERAL REGULATION (CFR) 75 FR 2012.
  
 3) THE VERTICAL WET VENT THE KITCHEN IS CONNECTED TO
 ALSO SERVES THE 2ND FLOOR BATHROOM. FBC-R P 3108.4 ONLY
 ALLOWS VERTICAL VENT VENTING TO BE ON THE SAME FLOOR.
 PLEASE REVISE YOUR SANITARY ISOMETRIC DRAWING.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION