2018-01-19 12:28:41 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. BREAKER FOR WATER HEATER IS STATED AS 30 AMP, WHICH |
| IS TOO LARGE FOR THIS LOAD. BREAKER SHOULD BE SIZED AT |
| 125% OF THE LOAD, WHICH IS A 25 AMP. PROVIDE |
| CORRECTION. NEC 422.13; FBC RE3702.10 |
| 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE3609.3 |
| 3. PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN GARAGE, |
| INCLUDING THE GARAGE DOOR OPENER. NEC 210.8; FBC |
| RE3902.2 |
| 4. ALL EXTERIOR RECEPTACLES REQUIRE GFCI PROTECTION. |
| PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.3 |
| 5. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE |
| PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH |
| CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE |
| CORRECTION. NEC 210.11(C)(3) , FBC RE3703.4 |
| 6. ALL RECEPTACLES IN KITCHEN REQUIRE GFCI PROTECTION. |
| PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.6 |
| 7. PROVIDE GFCI PROTECTED RECEPTACLE ON 2ND FLOOR |
| BALCONY. NEC 210.52(E)(3); FBC RE3901.7, E3902.3 |
| 8. ADDRESS ON PERMIT APPLICATION IS 457 LILAC CT., PLAN |
| SHOWS NO ADDRESS. PROVIDE CORRECTION. FBC 107.2.1 |
| 9. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 |
| 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 |
| 11. FEED TO INTERIOR PANEL FROM DISCONNECT IS REQUIRED |
| TO HAVE AN EQUIPMENT GROUNDING CONDUCTOR, SIZED PER |
| CODE. PROVIDE CORRECTION. NEC 250.122; FBC RE E3704.6, |
| 3607.3.1 |
| 12. PROVIDE SMOKE ALARM ON EACH STORY OF THE DWELLING. |
| FBC R314.3 |
| 13. PROVIDE LOCATION OF METER AND DISCONNECT ON PLAN. |
| FBC 107.2.1 |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |