2018-01-25 17:59:42RESIDENTIAL (R3) ADDITION/ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 6TH EDITION (2017).
  
 1- ENGINEER OF RECORD TO PROVIDE COMPLETE EQUIPMENT
 SIZING CALCULATIONS (2 COPIES) SIGNED AND SEALED AS
 REQUIRED BY FS CHAPTER 471. SEC. M1401.3
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 2- SHEET M0.1:
 A) SCOPE OF WORK IS INCORRECT. THIS IS A SINGLE FAMILY
 RESIDENCE NOT MEDICAL OFFICE. REVISE AS REQUIRED TO
 MATCH ARCHITECTURAL PLANS. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B) REVISE THE ROOF INSULATION SHOWN ON THE DESIGN
 CRITERIA TO MATCH ARCHITECTURAL PLANS. SEE ROOF LEGEND
 ON SHEET A-1.30 AND REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 3- SHEET M0.2: INFORMATION ON THE EXHAUST FAN SCHEDULE
 DOESN'T MATCH NUMBER OF BATHROOMS SHOWN ON PLANS.
 MISSING THE POWDER ROOM AND THE DUCT SIZE DOESN'T
 MATCH. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  