2018-01-18 14:21:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM STATES TO CONNECT TO SPARE METER.
 THERE SHOULD NOT BE ANY SPARE METERS, ONLY ONE SERVICE
 PER RESIDENTIAL ADDRESS IS PERMITTED. PROVIDE
 CORRECTION AND/OR CLARIFICATION. FBC 107.2.1; NEC
 230.2; FBC RE E3601.2
 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 3. SERVICE GROUNDING ELECTRODE TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.56; FBC RE E3608.4
 4. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14
 5. DINING ROOM LIGHT IS SHOWN ON THE SAME CIRCUIT AS
 THE DINING ROOM RECEPTACLE OUTLETS, WHICH IS A CODE
 VIOLATION. PROVIDE CORRECTION. NEC 210.52(B)(2); FBC RE
 E3703.2
 6. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE
 CORRECTION FOR MASTER ALL BATHROOMS, INCLUDING CIRCUITS
 A-15, A-17, AND A-23. NEC 210.11(C)(3) , FBC RE E3703.4
 7. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  