Plan Review Notes
Plan Review Notes For Permit 17120958
Permit Number 17120958
Review Stop B
Sequence Number 1
Notes
Date Text
2018-01-24 16:59:13RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS.
 CODE: FBC 6TH EDITION (2017).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
 NOTE: THIS MAY BE DONE LATER AT TIME OF PERMIT PRINTING
 WHEN PLANS ARE APPROVED AND STAMPED.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ALL NEW WINDOW TYPES AS SPECIFIED ON PLANS.
  
 B) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY
 SPECIFY WINDOW MULLION SIZES TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES.
  
 C) ALL NEW EXTERIOR DOORS AS SPECIFIED ON PLANS.
  
 D) HURRICANE SHUTTERS IF WINDOWS AND DOORS WITH GLAZING
 DON'T HAVE IMPACT GLASS. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE. SEE CITY SAMPLE.
  
 E) ROOF TILE AS SPECIFIED ON PLANS.
  
 F) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD. SEE ROOF TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES.
  
 G) FLAT ROOF ASSEMBLY. AND CLEARLY IDENTIFY SPECIFIC
 APPROVED INSULATED ASSEMBLY AND NON-INSULATED ASSEMBLY
 AS SPECIFIED ON ROOF LEGEND ON SHEET A-1.30. NOTE: IF
 SELECTED ASSEMBLIES DON'T MEET THE DESIGN PRESSURES OF
 ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS WILL BE REQUIRED.
  
 H) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 I) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 LIST THE CURRENT FLORIDA PRODUCT APPROVAL NUMBER NEXT
 TO EACH SPECIFIED CONNECTOR.
 NOTE: FLORIDA PRODUCT APPROVALS LISTED ON THE TRUSS TIE
 DOWN SCHEDULE ON SHEET S-2 NEED TO BE UPDATED TO THE
 CURRENT 2014 CODE.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 4- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY NUMBER OF SCREWS AND
 SIZE. IF SPECIFYING ADHESIVE, THEN PRODUCT APPROVAL IS
 REQUIRED.
  
 5- SHEET S-2:
 A) ROOF WIND LOADS SHOWN ON THE COMPONENT & CLADDING
 WIND DESIGN PRESSURES TABLE FOR ROOF ZONE #3 DON'T
 CORRESPOND TO ROOF ZONE #3. REVISE AS REQUIRED. TABLE
 R301.2(2) FBC-RESIDENTIAL, 5TH EDITION (2017).
 NOTE: SEE PLANS FOR TYPE OF ROOF AND REVISE DESIGN
 PRESSURES AS REQUIRED.
  
 B) WALL WIND LOADS SHOWN ON THE COMPONENT & CLADDING
 WIND DESIGN PRESSURES TABLE ARE TOO LOW FOR A BUILDING
 IN EXPOSURE "C". REVISE AS REQUIRED OR PROVIDE COMPLETE
 CALCULATIONS. TABLE R301.2(2) FBC-RESIDENTIAL.
  
 C) REVISE CORNER DISTANCE "A". ACCORDING TO NOTE "A" OF
 FIGURE R301.2(7) FBC-RESIDENTIAL THE MINIMUM DIMENSION
 FOR "A" IS 4'-0".
  
 6- STOOP DETAIL #2 ON SHEET A-1.00: SPECIFY THE
 DIMENSION OF THE TREAD AND LANDING. SEC. R311.7.5.2 AND
 R311.3 FBC-RESIDENTIAL.
  
 7- ROOF PLAN ON SHEET A-1.30: SPECIFY THE OVERFLOW
 DRAINS AND SCUPPERS FOR BOTH NEW ROOF SECTIONS AS
 REQUIRED BY SEC. R903.4.1 FBC-RESIDENTIAL.
  
 8- WINDOW SCHEDULE ON SHEET A-5.00: CLEARLY SPECIFY
 TYPE OF WINDOWS (SINGLE HUNG, FIXED, ETC). WINDOW
 SCHEDULE DOESN'T SPECIFY TYPE OF WINDOWS. SEC. 107.2.1
 CITY AMENDMENTS.
  
 9- CARBON MONOXIDE ALARM SHOWN ON SHEET E1.1 DOESN'T
 COMPLY WITH SEC. R315.1 FBC-RESIDENTIAL. CARBON
 MONOXIDE ALARM NEED TO BE WITHIN 10'-0" OF EACH
 BEDROOM. BEDROOM #1 DOESN'T COMPLY. REVISE AS REQUIRED.
  