Plan Review Notes
Plan Review Notes For Permit 17120956
Permit Number 17120956
Review Stop P
Sequence Number 1
Notes
Date Text
2018-01-19 13:03:471ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO
 THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS
 PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER
 CLOSETS AND URINALS PROVIDED FOR MEN. PER FBC PL
 403.1.3
  
 2. SHT. P5.1 THE WATER CLOSETS ARE NOT VENTED PROPERLY
 IF A DRY VENT IS INSTALLED BETWEEN THE TWO MOST UP
 STREAM WATER CLOSETS THE SYSTEM WOULD COMPLY AS A
 CIRCUIT VENT. PER FBC PL 914.1
  
 3. THE FIXTURE BRANCH FOR THE SHOWERS IS NOT VENTED A
 DRY VENT BETWEEN THE TWO MOST UPSTREAM SHOWERS WILL
 COMPLY AS A CIRCUIT VENT. PER FBC PL 914.1
  
 4. SHOW TRAP PRIMERS ON THE FLOOR DRAINS ON THE THE
 ISOMETRIC DRAWING. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  