2018-01-24 17:54:18 | 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION |
| CODES |
| PERMIT #17120956 |
| 1/24/18 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| AC SYSTEM- C403.2.1 FBC-14 ENERGY CONSERVATION. |
| |
| 2) SUBMIT ENERGY CALCULATIONS FOR THE CHANGE OF |
| OCCUPANCY IN ACCORDANCE WITH SECTIONS C101.4.4 AND |
| C101.5.1. |
| |
| 3) M6.1: THE O/A CALCULATION SCHEDULE IS INACCURATE. |
| THE SCHEDULE INDICATES 9800 SF. FOR AHU-1 WHICH APPEARS |
| TO BE THE ENTIRE SPACE, HOWEVER THERE IS AN EXISTING |
| AHU SERVING THE LARGER PERCENTAGE OF THE SPACE. PLEASE |
| CORRECT AND REVISE THE SCHEDULE TO INCLUDE BREAKDOWN |
| CALCULATIONS FOR ALL OF THE VARIOUS ROOMS AND SPACES- |
| OPEN GYM, LIFTING ROOM, CARDIO, LOUNGE, WAITING, |
| STORAGE, LOBBY, CORRIDOR ETC. THESE ARE ALL CALCULATED |
| AT DIFFERENT RATES PER TABLE 403.3 |
| |
| 4) M6.1: THE EXHAUST AIR CALCULATION SCHEDULE IS |
| INDICATING EF-1 HOWEVER THERE IS NO EF-1 SHOWN ON THE |
| PLAN, AND THE 500 CFMS OF EXHAUST AIR SHOWN DOES NOT |
| MATCH THE 800 CFMS OF EXHAUST AIR SHOWN IN THE AIR |
| BALANCE TABLE. IT APPEARS THAT EXHAUST AIR FROM THE |
| JANITOR ROOM AND OTHER ROOMS AND SPACES ARE MISSING. |
| PLEASE CORRECT THESE CALCULATIONS. |
| |
| 5) M2.1: VERIFY THAT THERE ARE EXISTING SMOKE DETECTORS |
| IN THE RETURN AIR PLENUM OF THE EXISTING AHU- SEE |
| SECTIONS 606.2.1 AND 606.2.2. |
| |
| 6) M2.1: VERIFY THERE IS A MINIMUM 3' CLEARANCE FROM |
| THE ERV EXHAUST OUTLET TO THE DOORWAY OPENING- SECTION |
| 501.3.1(3) |
| |
| 7) M2.1: PROVIDE CONDENSATE DISPOSAL PLANS FOR THE |
| AHU'S. SHOW THE PIPING RUNS AND DISCHARGE LOCATIONS. |
| |
| 8) M6.1: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR |
| INSTALLATION OF THE ROOF TOP CONDENSER AND STAND- |
| SECTION 301.15. |
| |
| 9) SUBMIT THE NOA'S FOR THE AC STAND AND THE O/A |
| LOUVERS WITHY NSHOP DRAWING APPROVAL STAMPS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |