2018-01-24 17:54:181ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #17120956
 1/24/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEM- C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 2) SUBMIT ENERGY CALCULATIONS FOR THE CHANGE OF
 OCCUPANCY IN ACCORDANCE WITH SECTIONS C101.4.4 AND
 C101.5.1.
  
 3) M6.1: THE O/A CALCULATION SCHEDULE IS INACCURATE.
 THE SCHEDULE INDICATES 9800 SF. FOR AHU-1 WHICH APPEARS
 TO BE THE ENTIRE SPACE, HOWEVER THERE IS AN EXISTING
 AHU SERVING THE LARGER PERCENTAGE OF THE SPACE. PLEASE
 CORRECT AND REVISE THE SCHEDULE TO INCLUDE BREAKDOWN
 CALCULATIONS FOR ALL OF THE VARIOUS ROOMS AND SPACES-
 OPEN GYM, LIFTING ROOM, CARDIO, LOUNGE, WAITING,
 STORAGE, LOBBY, CORRIDOR ETC. THESE ARE ALL CALCULATED
 AT DIFFERENT RATES PER TABLE 403.3
  
 4) M6.1: THE EXHAUST AIR CALCULATION SCHEDULE IS
 INDICATING EF-1 HOWEVER THERE IS NO EF-1 SHOWN ON THE
 PLAN, AND THE 500 CFMS OF EXHAUST AIR SHOWN DOES NOT
 MATCH THE 800 CFMS OF EXHAUST AIR SHOWN IN THE AIR
 BALANCE TABLE. IT APPEARS THAT EXHAUST AIR FROM THE
 JANITOR ROOM AND OTHER ROOMS AND SPACES ARE MISSING.
 PLEASE CORRECT THESE CALCULATIONS.
  
 5) M2.1: VERIFY THAT THERE ARE EXISTING SMOKE DETECTORS
 IN THE RETURN AIR PLENUM OF THE EXISTING AHU- SEE
 SECTIONS 606.2.1 AND 606.2.2.
  
 6) M2.1: VERIFY THERE IS A MINIMUM 3' CLEARANCE FROM
 THE ERV EXHAUST OUTLET TO THE DOORWAY OPENING- SECTION
 501.3.1(3)
  
 7) M2.1: PROVIDE CONDENSATE DISPOSAL PLANS FOR THE
 AHU'S. SHOW THE PIPING RUNS AND DISCHARGE LOCATIONS.
  
 8) M6.1: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE ROOF TOP CONDENSER AND STAND-
 SECTION 301.15.
  
 9) SUBMIT THE NOA'S FOR THE AC STAND AND THE O/A
 LOUVERS WITHY NSHOP DRAWING APPROVAL STAMPS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  