Plan Review Notes
Plan Review Notes For Permit 17120956
Permit Number 17120956
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-12-29 16:15:42THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PROPOSED PROJECT CHANGES A BUSINESS OCCUPANCY TO
 AN ASSEMBY OCCUPANCY.
  
 SHEET A0.14 INDICATES EXIT DOORS 001, 002, 010 & 011.
 SHEET AO.13 INDICATES A DOOR SCHEDULE WHICH SHOWS
 VARIOUS HARDWARE SETS FOR THOSE DOORS. NO PANIC
 HARDWARE IS INDICATED
  
 PER NFPA 101, CHAPTER 12, NEW ASSEMBLY OCCUPNACIES:
  
 12.2.2.2 DOORS.
 12.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK
 ONLY IF THE LATCH OR LOCK IS PANIC HARDWARE OR FIRE
 EXIT HARDWARE COMPLYING WITH 7.2.1.7, UNLESS OTHERWISE
 PERMITTED BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS DOORS AS PERMITTED IN
 12.2.2.2.6.
  
 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5
 SHALL BE PERMITTED TO BE USED ON A SINGLE DOOR OR A
 SINGLE PAIR OF DOORS IF BOTH OF THE FOLLOWING
 CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE ASSEMBLY OCCUPANCY HAS AN OCCUPANT LOAD NOT
 GREATER THAN 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR
 MORE ARE RELEASED BY PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC FIRE
 CODE REFERENCES.
  
  
  
  
 2) SHEET A1.11- PATIO DOORS ARE INDICATED AROUND THE
 EXTERIOR OF THE PROJECT. THOUGH THESE DOORS ARE
 EXISTING THE HARDWARE SHALL BE INDICATED OF THE THE
 DOOR SCHEDULE.
  
 PLEASE INCLUDE ALL DOOR HARDWARE OF ALL PATIO DOORS ON
 THE DOOR SCHEDULE.
  
  
  
  
 3) SHEET AO.13 - THE DOOR SCHEDULE INDICATES HARDWARE
 ON SOME OF THE PATIO DOORS. HOWEVER, THEY APPEAR TO
 INDICATE EXITING OUT ONTO THE PATIO. WHAT TYPE OF
 HARDWARE IS ON THESE DOORS THAT ALLOWS THEM BACK IN?
 WHAT IS THE OCCUPANCY SPACE OF THE PATIO? WILL PEOPLE
 BE ALLOWED TO GATHER ON THE PATIO? IF THE OCCUPANCY
 TOTAL IS OVER 50 THE EXIT DOORS FROM THE PATION ARE
 REQUIRED TO SWING IN THE DIRECTION OF TRAVEL.
  
 PER NFPA 101, CHAPTER 7, MEANS OF EGRESS:
  
 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE OF THE SIDE-HINGED OR PIVOTED-SWINGING
 TYPE SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL
 UNDER ANY OF THE FOLLOWING CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR MORE, EXCEPT UNDER ANY OF THE FOLLOWING
 CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO SWING IN THE DIRECTION OF EGRESS TRAVEL
 WHERE PERMITTED BY 7.2.4.3.8.1 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING
 HEALTH CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS THE DOOR OPENING SERVES AN INDIVIDUAL
 LIVING UNIT THAT OPENS DIRECTLY INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD
 CONTENTS AREA
  
 IF THE PATIO DOORS ARE EXIT DOORS, THE EXIT PATH IS NOT
 INDICATED ON THE LIFE SAFETY PLAN. IF THESE DOORS DO
 NOT LEAD TO A DEFINED EXIT, THEY ARE NO EXIT DOORS. SEE
 # 6 BELOW.
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC FIRE
 CODE REFERENCES.
  
  
  
  
 4) SHEETS A 1.13 - NOTE # 7 INDICATES SOUND PANELS ON
 THE CEILING. THERE ARE NO INDICATIONS OF HOW THESE WILL
 BE FASTENED? THERE ARE NO MANUFACTURES SPECIFICATION
 SHEETS TO VERIFY INTERIOR FINISH CODE COMPLIANCE.
  
 PER NFPA 101, CHAPTER 12
  
 12.3.3 INTERIOR FINISH.
 12.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH SECTION 10.2.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 5) SHEET A1.11 - NOTE # 8 INDICATES FLOORING PER
 MANUFACTURESE SPECIFICATIONS. THE IS NO FLOORING
 DOCUMENT OR INDICATIONS THAT CAN BE EASYILY OR
 DIFNITIVELY IDENTIFIED.
  
 PER NFPA 101, CHAPTER 12
  
 12.3.3.5 INTERIOR FLOOR FINISH
 12.3.3.5.1 INTERIOR FLOOR FINSIH SHALL COMPLY WITH
 SECTION10.2.
 12.3.3.5.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES AND
 EXIT ACCESS CORRIDORS AND IN SPACES NOT SEPARATED FROM
 THEM BY WALLS COMPLYING WITH 12.3.6 SHALL BE NOT LESS
 THAN CLASS II.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 6) SHEET E 2.1 - THERE ARE EXIT SIGNS OVER THE PATIO
 DOORS LEADING OUT ONTO THE PATIO AREA. THERE IS NO
 DEFINED EXIT INDICATED FROM THIS PATION SPACE. THE LIFE
 SAFETY PLAN DOES NOT INDICATE A DEFINED EXIT FROM THE
 PATIO SPACE.
  
 IF THE PATIO AREA DOES NOT HAVE A DEFINED EXIT, THE THE
 EXIT SIGNS ABOVE THESE DOORS IN NOT APPLICABLE FROM THE
 INTERIOR. ON THE CONTRARY, THESE DOORS MAY NEED TO HAVE
 EXIT SIGN INDICATORS ON THE EXTERIOR LEADING IN.
  
 EITHER WAY IT IS NOT CLEAR IF A PERSON CAN EXIT THE
 PATIO AREA WITH THIS PLAN SUBMITTAL.
  
 PLEASE REVIEW AND CORRECT OR CLARIFY WITH DETAILS.
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  