2018-01-31 10:15:10 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE RISER DIAGRAM. NEC 215.5 |
| 2. PANEL C IS SHOWN BEING FED FROM PANEL B ON A 20 AMP |
| BREAKER. THE LOAD SHOWN FOR THIS PANEL EXCEEDS 20 AMPS. |
| PROVIDE CORRECTION. NEC 215.2 |
| 3. ALL RECEPTACLES INSTALLED WITHIN 6 FEET OF A SINK |
| REQUIRE GFCI PROTECTION. PROVIDE CORRECTION FOR LOUNGE, |
| ROOM 417. NEC 210.8(B)(5) |
| 4. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, |
| 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |