2017-12-29 07:56:33 | THE PLANS STATE THAT A NEW HANDICAPPED ACCESSIBLE |
| SHOWER, A NEW LAVATORY AND A NEW WATER CLOSET ARE TO BE |
| INSTALLED. IS IT YOUR INTENT TO ATTEMPT TO COMPLY WITH |
| THE REQUIREMENTS OF THE FLORIDA ACCESSIBILITY CODE TO |
| THE MAXIMUM EXTENT FEASIBLE? CLARIFY ON THE PLANS. IF |
| SO, THE FOLLOWING ITEMS ARE HANDICAPPED ACCESSIBILITY |
| CODE REQUIREMENTS FOR SHOWERS, LAVATORIES AND WATER |
| CLOSETS FROM THE 2014 FBC-ACCESSIBILITY CODE AND ARE |
| LISTED AS GUIDELINES FOR THIS PROJECT. I UNDERSTAND |
| THAT IT WILL BE PHYSICALLY IMPOSSIBLE TO COMPLY WITH |
| SOME OF THESE REQUIREMENTS FOR ACCESSIBILITY. I AM |
| ASSUMING THE NEW WATER CLOSET AND THE NEW LAVATORY ARE |
| REMAINING AT THEIR EXISTING LOCATIONS AND CONNECTING TO |
| EXISTING WATER AND DRAIN LINES. IF SO, PLEASE NOTE SUCH |
| ON THE PLANS. THE PLUMBING CODE ITEMS LISTED IN |
| COMMENTS #1, #8 AND # 12 ARE MANDATORY. |
| |
| 1) SHOW THE LENGTH AND WIDTH DIMENSIONS OF THE NEW |
| SHOWER ON THE PLANS. THE MINIMUM WIDTH OF THE SHOWER |
| SHALL BE 30 INCHES PER 2014 FBC-PLUMBING SEC.417.4 AND |
| SHALL BE A MINIMUM OF 900 SQUARE INCHES INTERIOR CROSS |
| -SECTIONAL AREA. |
| 2) THE PLANS NOTE THAT THE SHOWER IS TO BE HANDICAPPED |
| ACCESSIBLE. THE SHOWER APPEARS TO BE OF A STANDARD |
| ROLL-IN TYPE HANDICAPPED SHOWER COMPARTMENT. IF THAT IS |
| THE INTENT, THE SHOWER SHOULD BE A MINIMUM OF 30 INCHES |
| WIDE BY A MINIMUM OF 60 INCHES LONG PER THE FBC-ACCESS. |
| SEC.608.2.2. CLARIFY. |
| 3) A 30 INCH WIDE MINIMUM BY 60 INCH LONG MINIMUM |
| CLEARANCE SHOULD BE PROVIDED ADJACENT TO THE OPEN FACE |
| OF THE SHOWER COMPARTMENT. REFER TO 2014 FBC-ACCESS. |
| SEC.608.2.2.1 AAND FIGURE 608.2.1. |
| 4) SHOW THE LOCATION OF THE SHOWER CONTROLS ON THE |
| PLANS. WHERE A LAVATORY IS INSTALLED ON ONE 30 INCH |
| WIDE MINIMUM SIDE OF THE CLEARANCE AS NOTED IN COMMENT |
| #3, THE SHOWER CONTROLS SHALL NOT BE LOCATED ON THE |
| SAME SIDE AS THE LAVATORY. 2014 FBC- ACCESS., |
| SEC.608.2.2.1 - SEE EXCEPTION. |
| 5) PROVIDE DETAILS FOR GRAB BARS AND REINFORCEMENT. |
| THEY SHALL BE INSTALLED IN COMPLIANCE WITH THE 2014 FBC |
| SECS 608.3, 608.3.2. |
| 6) A SHOWER SPRAY UNIT SHALL BE PROVIDED IN COMPLIANCE |
| WITH 2014 FBC-ACCESS.SEC. 608.6. |
| 7) THE SHOWER THRESHOLD SHALL BE A 1/2 INCH HIGH |
| MAXIMUM PER THE 2014 FBC - ACCESS. SEC.608.7 AND SEC. |
| 303. |
| 8) THE TILE WALL AREA OF THE SHOWER COMPARTMENT SHALL |
| BE CONSTRUCTED TO A HEIGHT NOT LESS THAN 6 FEET ABOVE |
| THE ROOM FLOOR LEVEL AND NOT LESS THAN 70 INCHES WHERE |
| MEASURED FROM THE SHOWER COMPARTMENT FLOOR AT THE |
| DRAIN. 2014 FBC-PLUMBING SEC.417.4.1. |
| 9) THE HEIGHT OF THE LAVATORY SHALL BE LOCATED A |
| MAXIMUM OF 34 INCHES ABOVE THE FINISH FLOOR TO THE |
| LAVATORY RIM. 2014 FBC_ ACCESS. SEC.606.3. |
| 10) EXPOSED WATER SUPPLY AND DRAIN PIPES UNDER THE |
| LAVATORIES SHALL BE INSULATED OR OTHERWISE CONFIGURED |
| TO PROTECT AGAINST CONTACT. 2014 FBC-ACCESS. SEC.606.5. |
| 11) THE SEAT HEIGHT OF A HANDICAPPED WATER CLOSET SHALL |
| BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM ABOVE THE |
| FINISH FLOOR MEASURED TO THE TOP OF THE SEAT. IN |
| RESIDENTIAL DWELLING UNITS THE MINIMUM HEIGHT IS |
| PERMITTED TO BE 15 INCHES MINIMUM AND 19 INCHES |
| MAXIMUM. |
| 12) THE SHOWER VALVE SHALL BE A BALANCED-PRESSURE, |
| THERMOSTATIC OR COMBINATION |
| BALANCED-PRESSURE/THERMOSTATIC VALVE PERR THE 2014 |
| FBC-PLUMBING SEC.424.3. |
| |