2018-01-26 09:52:15 | 1ST REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. SHT. A.0.1 AND A.0.2 PLEASE REMOVE DETAILS AND |
| REQUIREMENTS THAT DO NOT APPLY TO THIS PROJECT. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 2. A SEPARATE PERMIT IS REQUIRED FOR THE MAIN BACKFLOW, |
| GAS AND GREASE INTERCEPTOR IF A NEW ONE IS INSTALLED |
| PLEASE PLACE NOTE ON THE PLAN. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 3. THE EXISTING GREASE INTERCEPTOR SHALL BE CERTIFIED |
| BY WPB UTILITIES DEPT CONTACT JEFFERY ODOMS |
| 561-822-2172 OR [email protected]. PLEASE PLACE NOTE ON |
| PLAN. PER WPB AMEND TO FBC 107.2.1 |
| |
| 4. SHOW ON PLAN, THE MAIN BACKFLOW SHALL BE INSTALLED |
| NEXT TO THE WATER METER. PER WPB CROSS CONNECTION |
| MANUAL |
| |
| 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| CONFORMS TO ASSE 1070 OR CSA B125.3. MOST OF THESE ARE |
| POINT OF USE. |
| PER FBC PL 416.5 |
| |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |