Plan Review Notes
Plan Review Notes For Permit 17120895
Permit Number 17120895
Review Stop E
Sequence Number 1
Notes
Date Text
2018-01-23 13:15:36CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ESTIMATED AIC INFORMATION IS NOT ACCEPTABLE. PROVIDE
 AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH PANEL
 INCLUDING INFORMATION FROM THE POWER COMPANY STATING
 WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE
 SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9,
 110.10
 2. BASED ON THE CURRENT AIC CALCULATIONS, PANELS M AND
 B DO NOT MEET OR EXCEED THE RATING REQUIRED. WHEN
 ACCURATE CALCULATION IS COMPLETED, CONFIRM THAT ALL
 PANELS HAVE THE PROPER AIC RATING. NEC 110.9
 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 4. CIRCUIT B-23,25 SHOWS #12 WIRE ON A 25 AMP BREAKER
 FOR THE COFFEE MAKER. THE OCP FOR #12 WIRE SHALL NOT
 EXCEED THE VALUES IN 240.4(D). PROVIDE CORRECTION. NEC
 240.4(D)
 5. BASED ON THE AREA DESIGNATED FOR "NO ELECTRICAL
 CONDUIT IN HOOD AREA" ON SHEET E-2, IT APPEARS THAT
 THERE IS ELECTRICAL OUTLETS UNDER THE HOOD THAT WILL
 NOT BE SHUT OFF DURING HOOD SHUTDOWN. I SEE A NOTE ON
 SHEET E-5 UNDER "HOOD VENTILATION SYSTEM" THAT CALLS
 FOR ALL CONTROLLED COOKING EQUIPMENT UNDER HOOD TO BE
 SHUT DOWN, BUT THIS SHOULD INCLUDE ALL ELECTRICAL UNDER
 HOOD. THIS APPEARS TO INCLUDE CIRCUITS M-2,4,6; B-4;
 B-18; B-20; B-37; AND B-41. PROVIDE CLARIFICATION
 AND/OR CORRECTIONS AS NEEDED. NFPA 96, SECTION 10.4.1,
 FBC 107.2.1
 6. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  