Plan Review Notes For Permit 17120885
Permit Number 17120885
Review Stop P
Sequence Number 3
Notes
Date Text
2018-02-01 06:28:20AT THIS POINT, I HAVE NO IDEA WHAT THIS APPLICATION IS
 FOR.
 1) THE PERMIT APPLICATION STATES THE DESCRIPTION OF
 WORK IS FOR A GREASE TRAP BUT ONE SET OF PLANS SHOWS AN
 OIL/GREASE INTERCEPTOR AND ANOTHER SET OF PLANS SHOWS
 AN OIL SEPARATOR. WHICH IS IT? CHANGE THE DESCRIPTION
 OF WORK ON THE PERMIT APPLICATION.
 2) REMOVE ALL OLD PLANS AND SPECIFICATIONS FFROM THE
 PERMIT PACKAGE AND SUBMIT TWO COMPLETE SETS OF PLANS
 THAT CLEARLY REFLECT THE SCOPE OF WORK TO BE DDONE. WPB
 AMEND. TO FBC SEC. 107.2.1.2014 .
 3) YOU HAVE SUBMITTED COPIES OF DETAILS OF A TANK FROM
 FLORIDA SEPTIC INC. THE DETAILS STATE THAT THE TANK
 COMPLIES WITH SEC. 1003.5.1 OF THE 2014 FLORIDA
 PLUMBING CODE. THERE IS NO SUCH CODE SECTION IN THE
 PLUMBING CODE AND SEC. 1003.5 IS FOR GREASE
 INTERCEPTORS. CLARIFY.
 4) OIL SEPARATOR DESIGN SHALL COMPLY WITH 2014
 FBC-PLUMBING SEC.1003.4.2, 1003.4.2.1. THERE IS A NOTE
 ON THE SPECIFICATIONS FROM FLORIDA SEPTIC THAT THE
 TREATMENT RECEPTACLE HAS BEEN DESIGNED, CONSTRUCTED AND
 STRUCTURUALLY TESTED IN ACCORDANCE WITH CHAPTER
 64E-6.013, FL. ADMIN. CODE. THE F.A.C. DOES NOT APPLY
 TO OIL SEPARATORS. CLARIFY.
 5) THE PLAN SHEET C.1 SHALL BEAR THE SEAL AND WET
 SIGNATURE OF THE ARCHITECT OF RECCORD IN ACCORDANCE
 WITH FL. ADMIN. CODE RULE 61G1-16.003.
  
 NOTE: THE NEXT PLAN REVIEW SUBMITTAL SHALL BE SUBJECT
 TO A RESUBMITTAL FEE OF 4 TIME THE AMOUNT APPLIED TO
 THE PLAN REVIEW FEE PER FL. STATUTE 553.80 (2) (B).
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW