2018-01-23 10:48:10PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE A MECHANICAL EQUIPMENT SCHEDULE ON THE
 PLANS. SPECIFY THE EQUIPMENTS MODEL NUMBERS, SEER,
 CFMS, BTUS, ETC. FBC 107.3.5.3
  
 2) THE CFMS ARE NOT CONSISTENT BETWEEN THE PLANS AND
 THE ENERGY FORMS. ON THE PLANS THE AHU SIZE IS LISTED
 AS 800 CFM, THE CFMS ON THE MECHANICAL PLAN TOTAL 1400
 CFMS, THE EQUIPMENT SIZING CALCULATIONS LIST 780 CFMS
 AND THE ENERGY FORM R405-2014 HAS 720 CFMS. FBC 107.2.1
  
 3) THE EQUIPMENT SEER IS ALSO NOT CONSISTENT. THE
 ENERGY FORM R405-2014 HAS 16 SEER, THE EQUIPMENT
 SCHEDULE ON THE MECHANICAL PLAN HAS 17.0 SEER AND THE
 EQUIPMENT SIZING CALCULATIONS LIST 0 SEER. FBC 107.2.1
  
 4) SHOW THE DRYER EXHAUST DUCT ON THE MECHANICAL PLANS.
 M1502
  
  
  