2018-01-23 10:48:10 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) PROVIDE A MECHANICAL EQUIPMENT SCHEDULE ON THE | | PLANS. SPECIFY THE EQUIPMENTS MODEL NUMBERS, SEER, | | CFMS, BTUS, ETC. FBC 107.3.5.3 | | | | 2) THE CFMS ARE NOT CONSISTENT BETWEEN THE PLANS AND | | THE ENERGY FORMS. ON THE PLANS THE AHU SIZE IS LISTED | | AS 800 CFM, THE CFMS ON THE MECHANICAL PLAN TOTAL 1400 | | CFMS, THE EQUIPMENT SIZING CALCULATIONS LIST 780 CFMS | | AND THE ENERGY FORM R405-2014 HAS 720 CFMS. FBC 107.2.1 | | | | 3) THE EQUIPMENT SEER IS ALSO NOT CONSISTENT. THE | | ENERGY FORM R405-2014 HAS 16 SEER, THE EQUIPMENT | | SCHEDULE ON THE MECHANICAL PLAN HAS 17.0 SEER AND THE | | EQUIPMENT SIZING CALCULATIONS LIST 0 SEER. FBC 107.2.1 | | | | 4) SHOW THE DRYER EXHAUST DUCT ON THE MECHANICAL PLANS. | | M1502 | | | | | | |
|