2018-01-23 16:16:42 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) FBC-R311.6 REQUIRES THE MINIMUM WIDTH OF A HALLWAY |
| TO BE NOT LESS THAN 3 FEET. THE FLOOR PLAN DIMENSIONS |
| ON SHEET A-2 SHOWS A 2' 10-1/2" FINISH OPENING AREA IN |
| THE HALLWAY. |
| |
| 2) SHOW HOW THE OPENINGS BETWEEN THE SECTIONS WILL BE |
| FIREBLOCKED AS REQUIRED BY FBC-R 302.11. |
| |
| 3) THE SPACING OF THE OF THE INTERMEDIATE RAILS ON THE |
| PORCH ARE SPECIFIED ON THE PLANS AS HAVING A MAX. 4" |
| SPACE BETWEEN THEM. FBC-R312.1.3 REQUIRES THE OPENINGS |
| TO NOT ALLOW THE PASSAGE OF A SPHERE 4 INCHES IN |
| DIAMETER. |
| |
| 4) PROVIDE CALCULATIONS TO SHOW THAT THE REQUIRED |
| MINIMUM NET FREE AREA OF THE FOUNDATION VENTILATION |
| OPENINGS ARE IN COMPLIANCE WITH FBC-R 408.2. ONE CORNER |
| OF THE BUILDING DOES NOT HAVE A VENTILATION OPENING |
| WITHIN 3 FEET AS REQUIRED. |
| |
| 5) PROVIDE CALCULATIONS TO SHOW THAT THE REQUIRED NET |
| FREE VENTILATION AREA OF 1/300 OF ATTIC VENT RATIO AS |
| SPECIFIED ON THE ENERGY FORMS MEETS THE REQUIREMENTS OF |
| FBC-R806.2. |
| |
| 6) THE COMPLETE NAME OF THE INDIVIDUAL PREPARING THE |
| ENERGY FORM R405-2014 IS REQUIRED ON THE FORM PER 2014 |
| FBC ENERGY CONSERVATION SECTION R405.4.2 |
| |
| 7) THE SIGNATURE OF THE OWNER/AGENT IS REQUIRED ON THE |
| ENERGY FORM R405-2014 IS REQUIRED ON THE FORM PER 2014 |
| FBC ENERGY CONSERVATION SECTION R103.1.1.2 |
| |
| 8) IN ORDER TO CLAIM THE CEILING FAN CREDIT ON THE |
| ENERGY FORM R405-2014, THE SIZES OF THE CEILING FANS |
| WILL NEED TO BE SHOWN ON THE PLANS. 2014 FBC ENERGY |
| CONSERVATION SECTION R405.7.6 THE SIZES OF THE FANS ARE |
| BASED ON THE LONGEST WALL IN THE ROOM PER TABLE |
| R405.7.6. |
| |
| 9) THE SOIL REPORT UPLOAD IS A BLANK PAGE. PLEASE |
| CLARIFY. FBC 107.2.1 |
| |
| 10) UPDATE THE PRODUCT APPROVAL NUMBER THAT IS LISTED |
| ON THE PLANS FOR THE LOMANCO 700 SERIES ROOF VENTS TO |
| MATCH THE PRODUCT APPROVAL THAT WAS SUBMITTED (NOA NO. |
| 16-0510.28). FBC 107.2.1 |
| |
| 11) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE |
| HARDIE PLANK (NOA NO.17-0406.06) ALLOWS A MAXIMUM STUD |
| SPACING OF 16" O.C. AND THE WALL SECTION ON THE PLANS |
| HAS 2X4 STUDS AT 24" ON CENTER. SUBMIT ANOTHER PRODUCT |
| APPROVAL OR REVISE STUD SPACING. FBC 107.2.1 |
| |
| 12) NOTE: BLOWER DOOR TESTING IS REQUIRED FOR |
| RESIDENTIAL BUILDINGS OR DWELLING UNITS PERMITTED ON OR |
| AFTER JULY 1, 2017. |
| |
| 13) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| |