Plan Review Notes
Plan Review Notes For Permit 17120880
Permit Number 17120880
Review Stop B
Sequence Number 1
Notes
Date Text
2018-01-23 16:16:42PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R311.6 REQUIRES THE MINIMUM WIDTH OF A HALLWAY
 TO BE NOT LESS THAN 3 FEET. THE FLOOR PLAN DIMENSIONS
 ON SHEET A-2 SHOWS A 2' 10-1/2" FINISH OPENING AREA IN
 THE HALLWAY.
  
 2) SHOW HOW THE OPENINGS BETWEEN THE SECTIONS WILL BE
 FIREBLOCKED AS REQUIRED BY FBC-R 302.11.
  
 3) THE SPACING OF THE OF THE INTERMEDIATE RAILS ON THE
 PORCH ARE SPECIFIED ON THE PLANS AS HAVING A MAX. 4"
 SPACE BETWEEN THEM. FBC-R312.1.3 REQUIRES THE OPENINGS
 TO NOT ALLOW THE PASSAGE OF A SPHERE 4 INCHES IN
 DIAMETER.
  
 4) PROVIDE CALCULATIONS TO SHOW THAT THE REQUIRED
 MINIMUM NET FREE AREA OF THE FOUNDATION VENTILATION
 OPENINGS ARE IN COMPLIANCE WITH FBC-R 408.2. ONE CORNER
 OF THE BUILDING DOES NOT HAVE A VENTILATION OPENING
 WITHIN 3 FEET AS REQUIRED.
  
 5) PROVIDE CALCULATIONS TO SHOW THAT THE REQUIRED NET
 FREE VENTILATION AREA OF 1/300 OF ATTIC VENT RATIO AS
 SPECIFIED ON THE ENERGY FORMS MEETS THE REQUIREMENTS OF
 FBC-R806.2.
  
 6) THE COMPLETE NAME OF THE INDIVIDUAL PREPARING THE
 ENERGY FORM R405-2014 IS REQUIRED ON THE FORM PER 2014
 FBC ENERGY CONSERVATION SECTION R405.4.2
  
 7) THE SIGNATURE OF THE OWNER/AGENT IS REQUIRED ON THE
 ENERGY FORM R405-2014 IS REQUIRED ON THE FORM PER 2014
 FBC ENERGY CONSERVATION SECTION R103.1.1.2
  
 8) IN ORDER TO CLAIM THE CEILING FAN CREDIT ON THE
 ENERGY FORM R405-2014, THE SIZES OF THE CEILING FANS
 WILL NEED TO BE SHOWN ON THE PLANS. 2014 FBC ENERGY
 CONSERVATION SECTION R405.7.6 THE SIZES OF THE FANS ARE
 BASED ON THE LONGEST WALL IN THE ROOM PER TABLE
 R405.7.6.
  
 9) THE SOIL REPORT UPLOAD IS A BLANK PAGE. PLEASE
 CLARIFY. FBC 107.2.1
  
 10) UPDATE THE PRODUCT APPROVAL NUMBER THAT IS LISTED
 ON THE PLANS FOR THE LOMANCO 700 SERIES ROOF VENTS TO
 MATCH THE PRODUCT APPROVAL THAT WAS SUBMITTED (NOA NO.
 16-0510.28). FBC 107.2.1
  
 11) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 HARDIE PLANK (NOA NO.17-0406.06) ALLOWS A MAXIMUM STUD
 SPACING OF 16" O.C. AND THE WALL SECTION ON THE PLANS
 HAS 2X4 STUDS AT 24" ON CENTER. SUBMIT ANOTHER PRODUCT
 APPROVAL OR REVISE STUD SPACING. FBC 107.2.1
  
 12) NOTE: BLOWER DOOR TESTING IS REQUIRED FOR
 RESIDENTIAL BUILDINGS OR DWELLING UNITS PERMITTED ON OR
 AFTER JULY 1, 2017.
  
 13) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  